RMO100G DIntrduction
By pushing
STOP
button test could be performed at any time. In case of test interruption by pushing the
STOP
button, the last measured result will remain saved in the internal memory.
Upon expiry of the selected test lasting time, the last result remains saved at selected memory location.
Note 1:
Choose test current so that for the expected resistance you have maximum value of it.
Note 2:
Using DV-Win enables
starting and controlling RMO100G from the PC. The results could
be stored to PC. Using DV-Win after testings enables result transfer from the internal
RMO100G memory to
PC.
Note 3:
At the start of the test (Single, Continuous and CC), a check of cables connection is done.
In case of disconnection, or erroneous polarity, an alarm is activated, and the error
message is shown on the display.
Voltage sense cables disconnection, occured during the test, will cause an erroreous
result. The display will not show this as an error message.
During tests the high continued DC current will heat up the test set. To prevent RMO100G
from overheating, duty cycles apply. The duty cycles depend on the used test current,
please refer to section "Duty Cycles".