25
RMO100G Error Messages
9.3 Error Message " Polarity"
This message is displayed if the polarity of measuring cables is incorrect.
In this case connect measuring cables correct and repeat the test.
9.4 Error Message "Change Current"
This message is displayed if during the test the voltage at the test object exceeds 5 V. In this case
reduce the test current and repeat the test.
9.5 Error Message "Overheat"
This message is displayed when RMO100G
‟s operating temperature rises too high due to a high
ambient temperature or, despite the duty cycle time control, too many high current tests were
performed in too short of a time.
In this case, wait for the test set to cool down and repeat the test.
9.6 Error Message "Malfunction"
If this message is shown on the display, or if RMO100G cannot be operated anymore at all, a
serious internal error occurred.
Please do not open RMO100G by yourself. Contact the IBEKO Power AB (refer to section
”Manufacturer Contact Information”).
Figure 9-5:
Error message
"Overheat"
Figure 9-3:
Error message
"Polarity"
Figure 9-4:
Error message
"Change Current"
Figure 9-6:
Error message
"Malfunction"