Battery Voltage Recorder BVR11
M-B011VR-202-EN
14
In case the value in the field “
Auto: No. of cells”
is equal to 0, the user should provide the string and cell limit
values by his/her choice.
Default
By selecting the Default option, all limits will be set to predefined values that correspond to the 2V cell type.
The cell voltage limits are set to 1,75 V and 2,35 V, and the string voltage limits are set for a 24 V battery
string to 21.00 V and 28,20 V.
Language
In the Language section, the user may select the displayed language.
Bluetooth
The Bluetooth communication is switched on by pressing ENTER when the Bluetooth entry box is selected.
The Bluetooth communication symbol appears in the upper right corner.
Figure 3-17:
The
Language
screen
Figure 3-16:
Limits
screen
– Automatic
calculation of String limits based
on entered number of cells