TPR 40, 15 kW - 19
Part No 9045
1. Ancor the pump to the concrete pad.
2. Remove the pump covers and assemble the protection
screen skirt if this is required (A).
3. Connect the ducting to both the inlet and the outlet.
Do not start the pump without having it connected to
the ductwork.
4. Th
e pump inlet should always be connected to a sepa-
rator with a fi lter unit (B). Th
e pump cannot tolerate
contaminated airfl ow .
5. Extra silencing can be installed if the outlet
sound level is to be lowered from approximately 75
dB(A) to approximately 62-64 dB(A). See Accessories
on page 24.
6. If the outlet is vertical, and exposed to the elements,
rain protection should be installed (C). Exhaust air can
be very hot, up to 150
O
C.
7. Electrical connections may only be performed by a
certifi ed electrician. A separate lockable disconnect
should be installed where it is readily accessible and
within view of the pump.
8. Th
ermal overload protection must be installed to vali-
date the warranty.
9. Th
e control panel must be equipped with an overload
protection that should be adjusted and tested by a
certifi ed electrician. Check for correct motor rotation.