background image

5

CAUTION 

(SEE SECTION 3.2.2: VERTICAL DOWNFLOW & HORIZONTAL RIGHT DISCHARGE      )

Unit must be reconfigured for vertical down or horizontal right supply air dis

-

charge applications. The coil must be repositioned so the vertical drainpan is 

on the bottom for vertical down discharge applications or the horizontal drip 

pan is below coil for horizontal right discharge applications. Failure to recon-

figure the unit for these applications can result in property damage and poor 

system performance.

CAUTION 

(SEE SECTION 3.3: AUXILIARY OVERFLOW PAN)

In compliance with recognized codes, an auxiliary drain pan must be 

installed under all equipment containing evaporator coils that are located in 

any area of a structure where damage to the building or building contents 

may occur as a result of an overflow of the coil drain pan or a stoppage in 

the primary condensate drain piping. See Section 6.3 of this manual for 

auxiliary horizontal overflow pan accessory information (model RXBM). 

NOTICE

When used in cooling applications, excessive sweating may occur when unit 

is installed in an unconditioned space. This can result in property damage.

WARNING 

(SEE SECTION 3.7: AIR FILTER)

Do not operate the system without filters. A portion of the dust entrained in 

the air may temporarily lodge in the duct runs and at the supply registers. Any 

circulated dust particles could be heated and charred by contact with the heat-

ing elements. This residue could soil ceilings, walls, drapes, carpets and other 

articles in the house.

Soot damage may occur even with filters in place when certain types of can

-

dles, oil lamps or standing pilots are burned.

WARNING 

The first 36 inches of supply air plenum and ductwork must be constructed 

of sheet metal as required by NFPA 90B. The supply air plenum or duct must 

have a solid sheet metal bottom directly under the unit with no openings, reg-

isters or flexible air ducts located in it. If flexible supply air ducts are used they 

may be located only in the vertical walls of a rectangular plenum, a minimum 

of 6 inches from the solid bottom. Metal plenum or duct may be connected 

to the combustible floor base, if not, it must be connected to the unit supply 

duct flanges such that combustible floor or other combustible material is not 

exposed to the supply air opening from the downflow unit. Exposing combus

-

tible (non-metal) material to the supply opening of a downflow unit can cause 

a fire resulting in property damage, personal injury or death.

Exceptions to downflow warnings:

•  Installations  on  concrete  floor  slab  with  supply  air  plenum  and  ductwork 

completely encased in not less than 2 inches of concrete (See NFPA 90B).

NOTICE

Improper installation, or installation not made in accordance with the Underwriters 

Laboratory (UL) certification or these instructions, can result in unsatisfactory 

operation and/or dangerous conditions and are not covered by the unit warranty. 

WARNING

PROPOSITION 65: 

This appliance 

contains fiberglass insulation. 

Respirable particles of fiberglass 

are known to the State of California 

to cause cancer.
All manufacturer products meet 

current Federal 

OSHA

 Guidelines for 

safety. California Proposition 65 

warnings are required for certain 

products, which are not covered by 

the 

OSHA

 standards.

California’s Proposition 65 requires 

warnings for products sold in 

California that contain or produce 

any of over 600 listed chemicals 

known to the State of California to 

cause cancer or birth defects such 

as fiberglass insulation, lead in 

brass, and combustion products 

from natural gas.
All “new equipment” shipped for 

sale in California will have labels 

stating that the product contains 

and/or produces Proposition 65 

chemicals. Although we have not 

changed our processes, having the 

same label on all our products facil-

itates manufacturing and shipping. 

We cannot always know “when, 

or if” products will be sold in the 

California market.
You may receive inquiries from cus-

tomers about chemicals found in, or 

produced by, some of our heating 

and air-conditioning equipment, or 

found in natural gas used with some 

of our products. Listed below are 

those chemicals and substances 

commonly associated with similar 

equipment in our industry and other 

manufacturers.
•  Glass Wool (Fiberglass) Insulation

•  Carbon Monoxide (CO).

• Formaldehyde

• Benzene
More details are available at the 

websites for 

OSHA

 (Occupational 

Safety and Health Administration), 

at 

www.osha.gov

 and the State of 

California’s OEHHA (Office of 

Environmental Health Hazard 

Assessment), at 

www.oehha.org

Consumer education is important 

since the chemicals and substanc-

es on the list are found in our daily 

lives. Most consumers are aware 

that products present safety and 

health risks, when improperly used, 

handled and maintained.

!

!

!

!

!

!

!

Summary of Contents for DRAH1T

Page 1: ...nstallation adjustment and operation of this unit Read these instructions thoroughly before attempting installation or operation Failure to follow these instructions may result in improper installatio...

Page 2: ...factured Homes 15 3 2 5 Installation in Corrosive Environments 16 3 2 6 Supporting Air Handler in Horizontal Applications 16 3 3 Auxiliary Overflow Pan 16 3 4 Clearances 16 3 5 Duct Flanges 17 3 6 Duc...

Page 3: ...5 4 6 Checking Indoor Air Flow 35 4 6 1 Estimating CFM Using External Static Pressure 35 4 6 2 Estimating CFM Using Electric HEat Temperature Rise 35 4 7 Checking Refrigerant Charge 36 5 0 COMPONENTS...

Page 4: ...aled to prevent depres surization of the space and possible migration of combustion byproducts including carbon monoxide into the living space WARNING SEE SECTION 3 6 DUCTWORK Do not under any circums...

Page 5: ...d to the supply air opening from the downflow unit Exposing combus tible non metal material to the supply opening of a downflow unit can cause a fire resulting in property damage personal injury or de...

Page 6: ...e in place Correct air flow setting for application Removing the coil and storing it in a clean safe place is highly recom mended until construction is completed and the outdoor unit is installed Clea...

Page 7: ...IVED Immediately upon receipt all cartons and contents should be inspected for transit dam age Units with damaged cartons should be opened immediately If damage is found it should be noted on the deli...

Page 8: ...y secure the third lead The air handlers are shipped from the factory with the proper indoor coil installed and cannot be ordered without a coil These air handlers do not have an internal filter rack...

Page 9: ...ID LINE CONNECTION COPPER SWEAT VAPOR LINE CONNECTION COPPER SWEAT 2111 16 105 16 SUPPLY AIR W A H 191 2 RETURN AIR OPENING SEE DUCT FLANGES SECTION 3 5 FOR INSTRUCTIONS DIMENSIONAL DATA MODEL SIZE RE...

Page 10: ...NT This product has been designed and manufactured to meet certified AHRI capacity and efficiency ratings with the appropriate outdoor units However prop er refrigerant charge proper airflow and refri...

Page 11: ...performed safely with nitrogen or a mixture of R 410A and nitrogen 3 1 3 QUICK REFERENCE GUIDE FOR R 410A R 410A refrigerant operates at approximately 60 higher pressure 1 6 times than R 22 Ensure th...

Page 12: ...n the sides of the cabinet for the mounting screws using the provided dimples as guides Note that the shorter coil support rail with no notch must be mounted on the left hand side to provide clearance...

Page 13: ...nsulation is caught in lug Tighten lug as tight as possible while holding circuit breaker Check wires and make sure each wire is secure and none are loose Repeat for left wire bundle in left top circu...

Page 14: ...rec ommended for all air handler applications but special attention should be paid to those installed in unconditioned spaces Duct sizing and airflow are critical and must be based on the equipment se...

Page 15: ...ing or a restricted coil drain line See Section 3 3 If an electric heater kit is installed be sure the breaker or disconnect cover is sealed tightly to the door panel 3 2 4 INSTALLATION IN MOBILE MANU...

Page 16: ...ent containing evaporator coils that are located in any area of a structure where damage to the building or building contents may occur as a result of an overflow of the coil drain pan or a stoppage i...

Page 17: ...that the system airflow be adequate Make sure supply and return ductwork grills filters accessories etc are accounted for in total resistance Refer to the airflow performance tables in this manual to...

Page 18: ...nded orifice size for various outdoor units Piston size installed at factory Correct piston for other tonnages will be included with the matching outdoor unit 3 9 REFRIGERANT LINE CONNECTIONS CHARGING...

Page 19: ...lation should be pulled back in place so it contacts the air handler cabinet to prevent condensate from forming on the cold tube and dripping off A loosely fitting zip tie placed around the insulation...

Page 20: ...t block service access to front of the unit Minimum clearance of 24 inches is required for filter coil or blower removal and service access Although the condensate drain pan is designed is designed to...

Page 21: ...d drain line after installation is complete Pour water into drain pan enough to fill drain trap and line Check to make sure drain pan is draining completely no leaks are found in drain line fittings a...

Page 22: ...the event of a short circuit and serve as a disconnect Circuit breakers installed within the unit do not provide over current protection of the supply wiring and therefore may be sized larger than th...

Page 23: ...0 35 RXBH 1724A13C 9 4 12 5 3 60 3 4 17 SINGLE 26 1 30 1 1 6 35 40 35 40 3617AS 208 240V RXBH 17 03J 2 25 3 0 1 60 1 3 0 SINGLE 10 8 12 5 2 8 17 20 20 20 3617AS 3621AM 3621AH 208 240V RXBH 1724 03J 2...

Page 24: ...0 0 32 37 35 40 RXBH 1724 05J 3 6 4 8 1 60 1 4 8 SINGLE 17 3 20 0 4 6 28 31 30 35 RXBH 1724 07J 5 4 7 2 1 60 2 3 6 SINGLE 26 0 30 0 4 6 39 44 40 45 RXBH 1724 10J 7 2 9 6 1 60 2 4 8 SINGLE 34 6 40 0 4...

Page 25: ...or load is included in single circuit or circuit 1 of multiple circuits Heater loads are balanced on 3 phase models with 3 or 6 heating elements only Electric heater kits are not permitted for use wit...

Page 26: ...wiring where the breakers apply has been UL approved for short circuit protection Ampacity not breaker size determines supply circuit wire size The ampacity listed on the unit rating plate and the Ma...

Page 27: ...performance operate the unit in the 3 to 7 in W C external static range Units should be applied with a minimum of 1 in W C external static pressure NOTE The air flow performance data tables see Sectio...

Page 28: ...Speed tap T1 is always dedicated to continuous fan operation and delivers approximately 50 of the speed tap T4 air flow Speed taps T2 T4 are for applications with an external static pressure up to 0...

Page 29: ...96 1017 480 977 461 935 441 671 725 764 809 852 153 168 174 180 188 1084 512 1040 491 1001 472 896 936 971 249 257 261 1068 504 1025 484 992 468 952 449 910 429 711 765 804 849 892 164 179 185 191 199...

Page 30: ...5 3 2 CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts 3621AH No Heat 5 10x10 1 2 Hp 373 2 Speed dual voltage 2 3621AH 18 kW Heat 5 10x10 1 2 Hp 373 2 Speed dual voltage 2 5 10x1...

Page 31: ...1x11 3 4 559 5 Speed 11x11 3 4 559 5 Speed 11x11 3 4 559 5 Speed 4 5 2 3 2 3 6024AS No Heater 6024AS with 30kW Heater 6024AS No heater 6024AS with 30kw heater CFM RPM Watts CFM RPM Watts 1625 767 1591...

Page 32: ...4 1069 374 379 386 396 408 423 440 1465 1423 1381 1338 1296 1254 1212 779 816 854 891 929 967 1004 257 270 281 287 290 289 285 CFM RPM Watts 5 1803 1760 1217 1683 1648 1612 1576 886 919 952 988 1019 1...

Page 33: ...and Y inputs from the thermostat are de energized A time delay programmed into the DRAH1T motor keeps the blower motor energized for an additional 30 seconds to extract the residual cooling from the c...

Page 34: ...o provide a 3rd stage of heat as needed When the thermostat call is satisfied The G and Y terminals inputs from the thermostat are de energized A time delay programmed into the DRAH1T motor keeps the...

Page 35: ...ss the filter is accounted for The static pressure inside the supply plenum should be measured at a point about half way between the air handler and the first elbow or the end of the plenum Total exte...

Page 36: ...eration T2 T5 are for cooling heating operation and are selectable at the terminal block using a single wire with an insulated terminal that plugs onto the terminals in the ter minal block Speed chang...

Page 37: ...s through the blower access door The blower slides into place on a track and is secured by 4 sheet metal screws 5 5 TRANSFORMER A 40VA transformer is located inside the control box attached to the blo...

Page 38: ...e are no C Voltage air handlers available C voltage heater kits are for 3 phase applications and allow for smaller wire fuse breaker size compared to single phase J Voltage heater kits The heater kit...

Page 39: ...he system filter every ninety days or as often as found to be necessary and if obstructed clean or replace at once A qualified installer service agency or HVAC professional should instruct the homeown...

Page 40: ...mild solvent such as hot water and detergent Be careful not to disturb the balance weights clips on the blower wheel blades Do not drop or bend wheel as balance will be affected 7 4 MOTOR LUBRICATION...

Page 41: ...een the inlet orifice and outside of blower wheel Tighten setscrew on motor shaft Turn wheel by hand to make sure it runs true without hitting blower sides Reassemble motor wiring to capacitor and mot...

Page 42: ...V WULSSHG FKHFN IRU ORZ DLU IORZ 2YHU WHPSHUDWXUH OLPLW KDV IDLOHG UHSODFH 6HTXHQFHU RU FRQWDFWRU KDV IDLOHG UHSODFH 2QH RU PRUH KHDWLQJ HOHPHQWV KDYH EXUQHG RXW UHSODFH RLO LV IUR HQ XS 6 VWHP ORZ RQ...

Page 43: ...43 9 0 WIRING DIAGRAMS 9 1 WIRING DIAGRAM DRAH1T 208 240V 3 0 3 0 2 0 0 0 1 0 2 0 0 0 1 0...

Page 44: ...44 CM 0720...

Reviews: