Description of display

 

a) The displayed number corresponds to the concentration of detected target gas. This is updated

every 4 seconds.

b) The number of the sensor  for the displayed value. These scroll continuously through enabled

sensor channels.

c) This indicates whether the sensor is toxic (ppm) or explosive (LEL)

d) The Timer symbol indicates when the BX444Mc is in warm up phase as the sensor counts down to

full operation mode.

The Green display shows an absence of leakage of gas. 

This indicates a no gas 'normal' condition.

The Blue display shows percentage of Oxygen. This  

display shows a 'normal' condition.

The Red display shows an alarm condition where 

alarm 

Explosive

 gas threshold have been reached 

or passed. 

The Red display shows an alarm condition where 

alarm 

Toxic 

gas threshold have been reached or 

passed. 

The Yellow display shows an alarm condition 

where a a sensor fault exists on one or more 

sensors

w:

www.duomo.co.uk

-

e:

[email protected]

-

t:

01905 797989

-

f:

01905 774296

|

©

 

Duomo

 

(UK)

 

Ltd.

 

20

16

Summary of Contents for BX444-Mc

Page 1: ...esigned to be installed to EN60079 29 2 Operation When any connected sensor detects the presence of the target gas a 4 20mA signal is sent to the detector proportional to the level of gas The BX444 M then operates a pre alarm relay used for remote sirens or visual indicators If the level of gas continues to rise then the second pre alarm is actuated In the case of explosive gases when the level of...

Page 2: ...les duomo co uk t 01905 797989 f 01905 774296 Duomo UK Ltd 2016 Technical Specification Power Supply Secondary Battery Battery Charger max 2 2Ah Power consumption Power Consumption Relay contact range Pre alarm No 1 Pre alarm No 2 General alarm Sensor fault No of remote sensors Input signal Device precision Reaction time Control Unit Working temperature Start up self diagnostic delay Suitable for ...

Page 3: ...1 actuated This relay output de energises as the level of detected gas exceeds 13 LEL Natural Gas or 200ppm CO 9 2nd Pre Alarm At 13 LEL or 200ppm CO detected Pre alarm relay 2 actuated 10 Main Alarm 20 LEL concentration of gas detected Main alarm relay actuated 11 Fault Indicates a short circuit sensor fault loss of signal or incorrect connection of the sensor In case of a sensor failure the LED ...

Page 4: ...ts down to full operation mode The Green display shows an absence of leakage of gas This indicates a no gas normal condition The Blue display shows percentage of Oxygen This display shows a normal condition The Red display shows an alarm condition where alarm Explosive gas threshold have been reached or passed The Red display shows an alarm condition where alarm Toxic gas threshold have been reach...

Page 5: ...ly down When replacing sensors never seperate a sensing head from its PCB The sensor will have been calibrated using this particular board and therefore will not function correctly with any other Important Notes Always check the wiring before powering up the system Do not test this sensor with anything other than Duomo test gas see BX444 Mc Operation section for further information Concentrations ...

Page 6: ...hence the operation of the gas valve When it is ON the relay is in a normally open state When it is OFF the relay is in a normally closed state NOTE This affects how the gas valve operates and means that you may need to change how it is wired to the BX444 Mc Example shows Positive Safety on Switch 2 on 2nd DIP switch set Main Alarm relay actuation method This can be configured to provide either a ...

Page 7: ...nt Alarm LED s will light to show which zones are in alarm By releasing the the manual TEST button the lights will go out and the audible alarm will cease If a latched alarm function on the main relay is configured this will remain on until the RESET button is pressed 5 In order to conduct a full function test it is essential to use Duomo or equivalent calibrated test gas The maximum concentration...

Page 8: ...Main Alarm can be checked by pressing the TEST button on the detector fascia Check that the main alarm action is configured for a latching alarm Switch 2 on 5th DIP switch Check the sensor wiring If the red Overload LED is lit a short circuit or overload has occurred on the sensor or the connecting cable Ensure that there is not an occassional gas leak This may be due to a valve or joint which lea...

Page 9: ...that the commissioning is successful A Duomo Commissioning Certificate is provided It is prudent to make electrical connection to the detector terminal plus when withdrawn and leave the plug off the detector so that the Duomo Engineer is the first to power up the unit on site This allows wiring to be checked prior to commissioning and avoids damage due to incorrect connection Guarantees for this p...