c

 

Operation

Before

 

powering

 

up

 

the

 

BX444-M

c

 

once

 

again

 

check

 

that

 

all

 

electrical

 

connections

 

are

 

correct.
1. Apply 230V supply to the Ph and N terminals. Ensure that the correct fuse is used in the supply. (3 or 5A max.)

2. All of the lights on the fascia will light up in turn. This will take approximately 20 seconds. This checks the function of all
the LED's.

3. The ON LED will remain flashing for about 2 minutes. This is the sensor warm-up period. The gas detector will not
provide gas detection during this period. When the ON light becomes constant the detector is in operation.

4. By pushing and maintaining pressure on the manual TEST button a function test can be performed for all pre-alarm
relays and main alarm relay, together with LED's and audible alarm.

The sequence will be:

a) The 8% LEL / 120

ppm

and Pre-Alarm no. 1 LED will be actuated. The Pre-Alarm relay no.1 will be changed over and

terminals 6 and 7 will be connected.

b) The 13% LEL / 200

ppm

and Pre-Alarm no. 2 LED will be actuated. The Pre-Alarm relay no. 2 will be changed over and

terminals 8 and 9 will be connected and the audible alarm will continue to sound.

c) The 20% LEL / 300

ppm

and Main Alarm LED will be actuated. The Main Alarm relay will be changed over and terminals

10 and 11 will be connected, connection between terminals 10 and 12 will be broken and the audible alarm will continue
to sound. (When 'Intrinsic Safety' is on, terminals 10 and 11 will be broken and 10 and 12 will be connected). The relevant
Alarm LED's will light to show which zones are in alarm.

By releasing the the manual TEST button the lights will go out and the audible alarm will cease. If a latched alarm
function on the main relay is configured this will remain on until the RESET button is pressed.

5. In order to conduct a full function test it is essential to use Duomo or equivalent calibrated test gas. The maximum
concentrations are;

- 40% LEL for methane in air
- 350

ppm

for carbon monoxide

- 0.85% (MOL) for propane

Any

 

higher

 

than

 

this

 

can

 

reduce

 

sensor

 

life.

 

NOTE:

 

NEVER

 

TEST

 

USING

 

NEAT

 

GAS. THIS

 

WILL

 

POISON

 

THE

 

SENSOR.

6.

 

To

 

simulate

 

a

 

sensor

 

fault

 

situation

 

disconnect

 

the

 

sensor

 

plug.

 

The

 

detector

 

will

 

go

 

into

 

a

 

FAULT

 

alarm

 

and

 

the

 

sensor

 

fault

 

relay

 

will

 

be

 

actuated.

 

This

 

will

 

close

 

the

 

contacts

 

between

 

terminals

 

4

 

and

 

5

 

and

 

open

 

the

 

contacts

 

between

 

terminals

 

10

 

and

 

12

 

(Main

 

Alarm

 

relay). When

 

the

 

plug

 

is

 

reconnected

 

the

 

detector

 

can

 

be

 

reset.

w:

www.duomo.co.uk

-

e:

[email protected]

-

t:

01905 797989

-

f:

01905 774296

|

©

 

Duomo

 

(UK)

 

Ltd.

 

20

16

Switch

 

3

 

on

 

2nd DIP switch set

Determines

 

whether

 

the

 

audible

 

alarm

 

remains

 

operational

 

after

 

levels

 

have

 

dropped.

 

In

 

memory

 

mode,

 

the

 

alarm

 

remains

 

and

 

will

 

need

 

to

 

be

 

manually

 

reset.

 

In

 

non-memory

 

mode,

 

the

 

alarm

 

will

 

automatically

 

reset

 

after

 

levels

 

have

 

dropped.

Example

 

shows

 

memory

 

on

Switch 4 on 2nd DIP switch set

With switch 4 in the on position the BX444Mc is configured to indicate 
oxygen levels. The function is determined by setting either excess oxygen 
or oxygen depletion on the sensor itself (Duomo SGF104). 

IMPORTANT NOTE. 
If Oxygen setting is selected it is not possible to connect any other types of 
sensors for any other gases. For example natural Gas or CO

Summary of Contents for BX444-Mc

Page 1: ...esigned to be installed to EN60079 29 2 Operation When any connected sensor detects the presence of the target gas a 4 20mA signal is sent to the detector proportional to the level of gas The BX444 M then operates a pre alarm relay used for remote sirens or visual indicators If the level of gas continues to rise then the second pre alarm is actuated In the case of explosive gases when the level of...

Page 2: ...les duomo co uk t 01905 797989 f 01905 774296 Duomo UK Ltd 2016 Technical Specification Power Supply Secondary Battery Battery Charger max 2 2Ah Power consumption Power Consumption Relay contact range Pre alarm No 1 Pre alarm No 2 General alarm Sensor fault No of remote sensors Input signal Device precision Reaction time Control Unit Working temperature Start up self diagnostic delay Suitable for ...

Page 3: ...1 actuated This relay output de energises as the level of detected gas exceeds 13 LEL Natural Gas or 200ppm CO 9 2nd Pre Alarm At 13 LEL or 200ppm CO detected Pre alarm relay 2 actuated 10 Main Alarm 20 LEL concentration of gas detected Main alarm relay actuated 11 Fault Indicates a short circuit sensor fault loss of signal or incorrect connection of the sensor In case of a sensor failure the LED ...

Page 4: ...ts down to full operation mode The Green display shows an absence of leakage of gas This indicates a no gas normal condition The Blue display shows percentage of Oxygen This display shows a normal condition The Red display shows an alarm condition where alarm Explosive gas threshold have been reached or passed The Red display shows an alarm condition where alarm Toxic gas threshold have been reach...

Page 5: ...ly down When replacing sensors never seperate a sensing head from its PCB The sensor will have been calibrated using this particular board and therefore will not function correctly with any other Important Notes Always check the wiring before powering up the system Do not test this sensor with anything other than Duomo test gas see BX444 Mc Operation section for further information Concentrations ...

Page 6: ...hence the operation of the gas valve When it is ON the relay is in a normally open state When it is OFF the relay is in a normally closed state NOTE This affects how the gas valve operates and means that you may need to change how it is wired to the BX444 Mc Example shows Positive Safety on Switch 2 on 2nd DIP switch set Main Alarm relay actuation method This can be configured to provide either a ...

Page 7: ...nt Alarm LED s will light to show which zones are in alarm By releasing the the manual TEST button the lights will go out and the audible alarm will cease If a latched alarm function on the main relay is configured this will remain on until the RESET button is pressed 5 In order to conduct a full function test it is essential to use Duomo or equivalent calibrated test gas The maximum concentration...

Page 8: ...Main Alarm can be checked by pressing the TEST button on the detector fascia Check that the main alarm action is configured for a latching alarm Switch 2 on 5th DIP switch Check the sensor wiring If the red Overload LED is lit a short circuit or overload has occurred on the sensor or the connecting cable Ensure that there is not an occassional gas leak This may be due to a valve or joint which lea...

Page 9: ...that the commissioning is successful A Duomo Commissioning Certificate is provided It is prudent to make electrical connection to the detector terminal plus when withdrawn and leave the plug off the detector so that the Duomo Engineer is the first to power up the unit on site This allows wiring to be checked prior to commissioning and avoids damage due to incorrect connection Guarantees for this p...