Section D - Configuration, cont’d.
Two Basement Heat Pumps Plus One Gas Furnace
To configure two basement heat pumps plus one gas fur-
nace, ZONES need to be established. For explanation pur-
poses, the front unit will be ZONE 1, and the rear unit will
be ZONE 2. Zones can be arranged per the customer’s
wishes.
EACH unit must have 115V AC. Only one unit requires 12V
DC. Communications line must be between the Comfort
Control Center and ONE unit.
A second communications line must be connected between
the two units control boxes.
Two (2) furnace thermostat wires must be routed to ONE
unit.
For explanation purposes the 12V DC, Comfort Control
Center communications line and the two (2) furnace ther-
mostat wires are to ZONE 1 (front) unit.
FIG. D39
ZONE 1 configuration should have all Dip switches to
OFF position. The ambient sensor should be plugged
into P3 (red) connector.
ZONE 2 configuration should have Dip switch 5 (ZONE
2) to ON position and all other Dip switches to OFF
position. The ambient sensor should be plugged into
P3 (red) connector. The remote sensor should be
plugged into P4 (white) connector.
Note:
If a remote sensor is used, it must be plugged into
the P4 (white) connector.
Improper connections can cause component
damage.