Section D - Configuration, cont’d.
1. One Comfort Zone
One Rooftop Air Conditioner
To configure one rooftop air conditioner, all Dip switches
are to “OFF” position and the cold (freeze) control is plugged
into P5 (blue) connector. Two thermostat wires from the
furnace, communications line, AC power and DC power
are properly connected to the air conditioner control box.
Note:
If a remote sensor is used, it must be plugged into
the P4 (white) connector.
Improper connections can cause component
damage.
Typical installation for one comfort zone with rooftop air.
Comfort control may serve as a room temperature sensor,
or a remote sensor may be used.
One Rooftop Air Conditioner plus One Gas Furnace
To configure one rooftop air conditioner plus one gas fur-
nace, all Dip switches are “OFF” and the freeze control is
plugged into the proper connector (blue). Two thermostat
wires from the furnace, AC power, DC power and commu-
nication line are properly connected to the air conditioner
control box.
Note:
If a remote sensor is used, it must be plugged into
the P4 (white) connector.
Improper connections can cause component
damage.
FIG. D6
FIG. D3
FIG. D4
FIG. D5