7
TABLE #2: SERIES 90 PROPANE GAS
SERIES 90-50
Stock Factory
Btu Value of LP Gas++
Settings
2300
2350
2400
2450
2500
Altitude in Ft.
0-5,000
5,000-10,000
Normal Input (MBH)
50
–
–
–
–
–
Manifold Pressure In W.C.
2.5
3
3
2.5
2.5
2.5
Orifice
43331095
43331095
SERIES 90-75*
Stock Factory
Btu Value of LP Gas++
Settings
2300
2350
2400
2450
2500
Altitude in Ft.
0-5,000
5,000-10,000
Normal Input (MBH)
75
–
–
–
–
–
Manifold Pressure In W.C.
2.5
3.5
3.5
3.5
3
3
Orifice
43331093
43331096*
* For model 90-75 LP units only at altitudes above 5,000 ft., install 90-75 High Altitude Orifice Kit #550001810. For all other alti
-
tudes use factory installed orifice.
SERIES 90-100
Stock Factory
Btu Value of LP Gas++
Settings
2300
2350
2400
2450
2500
Altitude in Ft.
0-5,000
5,000-10,000
Normal Input (MBH)
100
–
–
–
–
–
Manifold Pressure In W.C.
2.5
3
3
3
2.5
2.5
Orifice
43331091
43331091
++Contact local gas utility or distributor for Btu value of gas.
boilers for use aT HigH alTiTude
NOTICE
For model 90-75 LP units only at altitudes
above 5,000 ft., install 90-75 high Altitude
Orifice Kit #550001810*. For all other
altitudes use factory installed orifice
.
Summary of Contents for 90-100
Page 13: ...13 Figure 3 Multi zone Boiler Piping With Zone Valves Near Boiler Piping...
Page 16: ...16 Figure 6 Diaphragm Type Expansion Tank Piping Near Boiler Piping...
Page 17: ...17 Figure 7 Conventional closed type Expansion Tank Piping Near Boiler Piping...
Page 23: ...23 Figure 11 Combustion Air and Vent Piping Combustion Air and Vent Pipe...
Page 27: ...27 Figure 13 Field Wiring Connections Electrical Wiring...
Page 44: ...44 Service Hints Detailed Sequence Of Operation...
Page 50: ...50 TROUBLESHOOTING CHART 2 Troubleshooting...
Page 53: ...53 TROUBLESHOOTING CHART 5 Troubleshooting...
Page 56: ...85 Middle Rd Dunkirk NY 14048...