27
CE60-3GSM - Installer
9.16.
Door Control
9.17.
Sensors Supervision
9.18.
Number of Vocal Calls
The dialler calls – for the number of times set – each number enabled: starting from the first, as many times as
requested, then moves to the next and so on.
After finishing, the call cycle will start sending SMS.
9.19.
AUX Relay Association
9.20.
Radio Saturation
Wireless Saturat
Yes
Num.Vocal Calls
1
Number of Vocal Calls (1 ÷ 9)
Set the number of calls that the control panel will make to
each phone number stored, in the case of alarm.
Each time you press "X" you increase the value.
AUX Relay Relat.
RELAY TEMPERATURE
Door Control
Yes
Door Control (Yes/No)
The control panel runs a check on all the zones to verify if
there are any “opened doors” at the moment it is armed
and signals an abnormal situation.
The signal lasts about 10 seconds.
Supervis.Enabled
No
Sensors Supervision (Si/No)
The control panel checks all the memorized sensors every
hour to make sure they are still operating. If a sensor does
not respond for three consecutive times within 12h, the
panel indicates "Supervision Failed”.
Radio Saturation Test
Press the "
X
" key to activate/deactivate the Radio Saturation
Test (see paragraph 13)
Rele AUX Assoc.
(see par. 8)
AUX Relay Relat.
RELAY TELEALARM
AUX Relay Relat.
RELAY RING
X
X
X
X
X
X
X
AUX Relay Relat.
RELAY ON/OFF
AUX Relay Relat.
RELAY Inib.Sir.P.
AUX Relay Relat.
RELE TC
X
X
X