Contatto
ModDMX
It is also possible to save into a file the scenery currently
displayed in the window (button To File); each file can con-
tain only one scenery, thus, if more sceneries have to be
saved, it is required to create more files; these ones must
have .DMX extension.
To recall a scenery from a file and display it on the window,
use the button From File.
On the right side of the window can be found the following
controls:
✗
Read and Program respectively to read the current
situation of ModDMX and report it into the window and
to transfer the values currently displayed on the win-
dow to ModDMX module
✗
ID & Ver. To show the FW version of ModDMX module
✗
From File and To File respectively to open a file con-
taining a scenery and to save the scenery currently
displayed in the window into a file
✗
All '0' to reset to 0 all the sliders
✗
Include All and Exclude All respectively to include or
exclude all channels from a scenery
✗
MIN and MAX to read (Read) or write (Program) re-
spectively the minimum and the maximum value as-
signed to ModDMX module
✗
Close to close the ModDMX tool
Mapping
MCP Ide allows to show the map of ModDMX module as in
the following figure:
The first text box on the top (1 in the example) is the ad-
dress of ModDMX which is communicating with MCP Ide.
Code
is the value of the code to be sent to to ModDMX
module (high byte of the Word to be sent, see the bus com-
mand table).
Val/Sc/Ch
is the value or the scenery number or the chan-
nel associated to the just explained Code (low byte of the
Word to be sent to the module).
The box DEC allows to change the entering method for
Code
and
Val/Sc/Ch
among decimal and hexadecimal;
with the mouse pointer on this box, right click and perform
the desired choice.
The command to the module (
Code
+
Val/Sc/Ch
) will be
sent only after the value for
Val/Sc/Ch
has been written
and confirmed by Enter on the keyboard.
As usual, the symbol of the module in the map will have
green background if it is connected and properly operating,
on the contrary the background will be in red color.
Technical characteristics
Supply voltage
24V
±
25% SELV
MAX current consumption
50mA
DMX channels
64
Managed DMX devices
32 MAX, suggested 16
Number of sceneries
64
Fade time
0 to 650.25 seconds, step 2.55
seconds
Operating temperature
-10
÷
+50
°
C
Storage temperature
-30
÷
+85
°
C
Protection degree
IP20
Outline dimensions
DUEMMEGI
s.r.l. - Via Longhena, 4 - 20139 MILANO
Tel. 02/57300377 - Fax 02/55213686 –
www.duemmegi.it
Rel.: 2.2 December 2013
Page 6 of 7
HOME AND BUILDING AUTOMATION
90
m
m
58mm
DUEMMEGI
ADDRESS
Contatto
MILANO-ITALY
DMX Gateway
Power supply 24V= ±25% / 50mA
MODDMX
ON
+2
4V
0V
L1
L2
P
13 14
16 17
15
1
2
3
A
(+
)
B
(-
)
G
DMX
TX
53mm