38
8.2.8 Over voltage or too low voltage protection diagnosis and solution(P1)
Error Code
P1
Malfunction decision
conditions
An abnormal voltage rise or drop is detected by checking the
specified voltage detection circuit.
Supposed causes
●
Power supply problems.
●
Wiring mistake
●
PCB faulty
Trouble shooting:
Check if the power supply is
normal.
Disconnect the unit with power supply and
try to restart the unit when power supply
gets normal.
Yes
Check if all the connections
and wires are good?
Correct the connections or
replace the wires.
Yes
Replace the IPM board if it is
separate with main PCB.
Yes
Replace outdoor main PCB.
Power on and when the unit is in
standby, check if the voltage between P
and N is around DC 310V, 340V, or
380V? For different kinds of units, the
voltage differs. Consult with technical
engineer to get definite value. Then
start up the unit, measure the voltage
between P and N. Is it in 220V~400V?
No
No
No