7.4 Operation Modes and Functions
7.4.1 Fan mode
(1) Outdoor fan and compressor stop.
(2) Temperature setting function is disabled, and no
setting temperature is displayed.
(3) Indoor fan can be set to
high/med/low/auto.
(4) The louver operates same as in cooling mode.
(5) Auto fan:
7.4.2 Cooling Mode
7.4.2.1 Compressor running rules
When T1-Ts<ΔT -2˚C, the compressor will stop,
when T1—Ts >ΔT -0.5˚C, the compressor will be
activated.
ΔT is the programmed parameter of
temperature compensation.
When the AC runs in mute mode, the compressor
will run with low frequency. When the current is
more than setting value, the current protection
function will be activated, and the compressor will
stop.
7.4.2.2 Outdoor fan running rules
The outdoor unit will run at different fan speeds
according to T4.
For different outdoor units, the fan speeds are
different.
7.4.2.2 Indoor fan running rules
In cooling mode, indoor fan runs all the time and the
speed can be selected as high, medium, low and
auto.
The indoor fan is controlled as below:
The auto fan acts as below rules:
7.4.2.4 Condenser temperature protection