8.2.2 Indoor / outdoor unit’s communication diagnosis and solution(E1)
Error Code
E1
Malfunction decision
conditions
Indoor unit does not receive the feedback from outdoor unit during
110 seconds and this condition happens four times continuously.
Supposed causes
●
Wiring mistake
●
Indoor or outdoor PCB faulty
Troubleshooting:
Power off, then restart the unit 2 minutes
later. Is the error extinguished?
No
Measure Vs. Is the voltage alternating
between -25V to 25V?
Yes
Check the outdoor wiring connection
。
Is the wiring correctly?
Yes
Check the indoor wiring connection.
Is the wiring correct?
Replace the reactor.
Is the reactor
normal?
Yes
Replace the outdoor main PCB.
Power on. Is the error
extinguished?
Replace the indoor main PCB.
Power on. Is the error
extinguished?
No
Replace the outdoor main PCB.
No
Replace the indoor main PCB
.
.
.
Yes
Yes
No