8.2.3 Fan speed has been out of control diagnosis and solution(E3)
Error Code
E3/F5
Malfunction decision
conditions
When fan speed keeps too low or too high for certain time, the
unit will stop and the LED will display the failure.
Supposed causes
●
Wiring mistake
●
Fan assembly faulty
●
Fan motor faulty
●
PCB faulty
Trouble shooting:
Shut off the power supply
and turn it on 2 minutes
later. Is it still displaying the
error code?
The unit operates normally.
Yes
Shut off the power supply,
rotate the fan by hand. Does
it rotate properly?
Yes
Find out the cause and have it
solved. For example, check
whether the fan is blocked or
the bearing is broken?
Check the wires of fan
motor. Are all the
connections good?
Correct the connections.
Yes
Check whether the main PCB is
normal through index 1?
Replace the main PCB
Yes
Replace the fan motor. Is the
error
extinguished?
No
No
No
No
No