13
ENGLISH
L2000651 Installation guide for DucoBox Silent (Revision N | 13.07.2020)
3
Press ‘HIGH’ or ‘LOW’ to activate the configuration mode for 30 minutes�
Then close the cover firmly.
Which configuration mode should I choose?
Button
Air calibration using 'HIGH'
This method is standard and has the
lowest consumption� Recommended
in the majority of homes�
Air calibration using 'LOW'
This method offers a boost mode
but may give rise to more noise
and higher consumption�
Low mode (10%)
Low mode (14-33%)*
Medium mode (50%)
High mode (100%)
High mode (100%)
Boost mode (143-333%)*
The percentages in the table indicate what percentage of the flow rate configured will be extracted�
The configuration mode chosen does not affect the operation of the AUTO mode�
* In the ‘LOW’ configuration, the percentage in low mode and boost mode is dependent on the type of
home (see section "06�D Setting type of home" on page 10) and limited to the maximum achievable
ventilation system flow rate�
HIGH
LOW
4
Close the DucoBox cover�
Ensure it forms an airtight seal with the DucoBox�
5
Select the duct with the highest flow rate and restriction�
6
Measure at the vent and adjust the DucoBox rpm until the desired flow rate is
obtained� This can be done in two ways:
• Using the (lower) and (higher) buttons on a paired User controller or CO
2
/
Humidity Sensor*�
• Using the ‘DOWN’ and ‘UP’ buttons on the DucoBox� This requires the cover to
be removed temporarily� Always close the cover after every measurement.
Pressing the buttons once is equal to 1% (= approximately 2 to 3 m3/h per press of the button depending
on the restriction in the ducts)�
/
/
7
Now measure the other vents� The flow rate from these other vents must only be
adjusted at the vents themselves.
8
Repeat steps
6
and
7
until the desired flow rate has been obtained at each vent�
9
Exit configuration mode� This can be done in two ways:
• Long-press ‘AUTO’ on a paired User controller or CO
2
/Humidity sensor* until
the 4 LEDs light up white briefly and then turn yellow again�
• Press ‘ENTER’ in the DucoBox and then immediately close the cover on the
DucoBox� If the cover was not closed, you can pull the plug out of the power
socket for a few seconds after closing the cover in order to reboot the DucoBox�
The DucoBox will now perform a calibration by speeding up high� This may take up
to 1�5 min� Calibration will be complete once the DucoBox slows down the ‘AUTO’
button LEDs on the User controllers / CO
2
/Humidity sensors* will turn white, as
will the LED on the DucoBox�
ENTER
* Depending on the software version of the User controller / CO
2
/Humidity sensor�