background image

10

ENGLISH 

L2000651 Installation guide for DucoBox Silent (Revision N | 13.07.2020)

06.B

Installer / User mode

To add components to the network, remove or replace, the system should be put in ‘Installer mode’� The LED on each component 

indicates the active mode of the component (see table in next section)�

‘Installer mode’ can be activated by pressing the DucoBox Silent ‘INST’ button (see drawing in section "04�A Connections & but-

tons" on page 8�) Once the LED on the master unit starts flashing, it means that ‘Installer mode’ is active� Press ‘INST’ again to 

return to ‘User mode’ (LED fully on or off)� The system reverts automatically to ‘User mode’ after 15 minutes of inactivity�

06.C

LED indications

RED (blinking slowly) 

Not in network

RED (blinking rapidly) 

Logging in

GREEN (blinking slowly) 

In network

GREEN (blinking rapidly) 

In network, waiting for associated components

YELLOW (clignotement rapide) 

Transitional phase (please wait)

YELLOW (on) Initialising (system 

configuration in progress)

WHITE or OFF 

Normal

BLUE 

Component is displayed if changes are being put through via the master�

ORANGE 

The system is not working correctly because the DucoBox has not been calibrated� Restart the 

DucoBox� Follow the guidelines in ‘10 essential tips’ if the problem recurs continually�

06.D

Setting type of home

Setting the type of home and number of occupants correctly will provide the ventilation system with a better basis to adjust the 

mid-position� There are two types of home: low-rise (e�g� a house) and high-rise (e�g� a flat)� Configuration of this component is 

obligatory in the Netherlands. The standard setting for a DucoBox is as a low-rise home for 4 (or more) occupants�

Setting type of home

1

Ensure that ‘Installer Mode’ has been activated (via the ‘INST’ button)�

2

Press ‘LOW’ for a low-rise or ‘HIGH’ for a high-rise home�

3

The yellow LED (see illustration) will flash in a pattern that indicates the 

number of occupants: Once, twice (applies for 3 occupants as well) or 4 

times (applies for 4 occupants or more)� Press ‘LOW’ or ‘HIGH’ respectively 

again until the LED pattern matches the correct number of occupants�

4

Press the ‘INST’ button to exit ‘Installer mode’�

or

HIGH

LOW

INST

Summary of Contents for DucoBox Silent 0000-4215

Page 1: ...Installation guide ENGLISH DucoBox Silent Product version 17xxxx and above Step by step instructions duco tv L2000651 Revision N 13 07 2020...

Page 2: ...ng type of home 10 06 E Pairing components 11 06 F Removing replacing components 11 06 H Tips 12 07 Air calibration 12 07 A Air calibration procedure for DucoBox Silent 12 07 B Checking 14 08 Maintena...

Page 3: ...extractor fan that exhausts stale air with excessive CO2 content or humidity On the other it is the system master or brain of the system It receives and interprets signals from slave components measu...

Page 4: ...reference 0000 4215 0000 4225 0000 4229 0000 4232 0000 4233 0000 4237 0000 4238 0000 4304 0000 4305 0000 4438 0000 4490 0000 4501 0000 4607 DucoBox Silent Indoor outdoor air tightness in m h Annual el...

Page 5: ...ergy consumption SEC in kWh m an SEC class Trade mark Duco Model reference 0000 5127 DucoBox Silent 325 Indoor outdoor air tightness in m h Annual electricity consumption AEC in kWh electricity a Annu...

Page 6: ...rgy consumption SEC in kWh m an SEC class Trade mark Duco Model reference 0000 5126 DucoBox Silent 225 Indoor outdoor air tightness in m h Annual electricity consumption AEC in kWh electricity a Annua...

Page 7: ...25 mm upward from 30 m h 100 mm less than 30 m h Or an equivalent based on a specific duct calculation p e for ducts placed in floor screed Make sure that the total counter pressure in the ducts is as...

Page 8: ...e refer to information sheet RF communication L8000018 at www duco eu for further information DUCO RF Power supply 230 VAC Wiring 1 5 mm Frequency 868 Mhz Maximum distance 350 m free field less throug...

Page 9: ...also enables problems in the system to be pinpointed The Duco Network Tool is issued to every installer after attending a free training course at the Duco Academy Please refer to our website or your D...

Page 10: ...ITE or OFF Normal BLUE Component is displayed if changes are being put through via the master ORANGE The system is not working correctly because the DucoBox has not been calibrated Restart the DucoBox...

Page 11: ...replacing is only possible within 30 minutes after the component is paired in or is restarted Restarting can be done by disconnecting the power for a moment After a time span of 30 minutes remove and...

Page 12: ...o eu for information about determining ventilation flow rates 07 A Air calibration procedure for DucoBox Silent The air calibration procedure must be carried out on a calm day no more than wind force...

Page 13: ...rate is obtained This can be done in two ways Using the lower and higher buttons on a paired User controller or CO2 Humidity Sensor Using the DOWN and UP buttons on the DucoBox This requires the cover...

Page 14: ...fter 15 minutes 08 Maintenance service Please refer to the maintenance instructions at www duco eu and view the videos on duco tv for more information For service problems as a user Please contact you...

Page 15: ...15 ENGLISH L2000651 Installation guide for DucoBox Silent Revision N 13 07 2020...

Page 16: ...Installed by L2000651 Document last modified on 13 07 2020 revision N...

Reviews: