A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
98
4.3 Specification of Power Supply Wire and Air Switch
Model
Power
Supply
Capability of Air
Switch(A)
(Outdoor/Indoor)
Minimum Sectional
Area
Of Earth Wire (mm
2
)
(Outdoor/Indoor)
Minimum Sectional
Area
Of power Wire
(mm
2
)
(Outdoor/Indoor)
GUHD09NK3CO 16/6
2.5/1.0 2.5/1.0
GUHD12NK3CO 16/6
2.5/1.0 2.5/1.0
GUHD18NK3CO 20/6
4.0/1.0 4.0/1.0
GUHD24NK3CO 20/10
4.0/1.5 4.0/1.5
GUHD30NK3CO 32/10
6.0/1.5 6.0/1.5
GUHD36NK3CO 32/10
6.0/1.5 6.0/1.5
GUHD42NK3CO 32/10
6.0/1.5 6.0/1.5
GUHD48NK3CO
220-240
V
~
50HZ
32/10 6.0/1.5 6.0/1.5
GUHD36NM3CO 20/10
4.0/1.5 6.0/1.5
GUHD42NM3CO 20/10
4.0/1.5 4.0/1.5
GUHD48NM3CO 20/10
4.0/1.5 4.0/1.5
GUHD60NM3CO
380-415V
3
N~
50Hz
20/10 4.0/1.5 4.0/1.5
Note
:
The parameters of the power cord listed above are only applicable to the BV single-core power cord which is laid
within the plastic bushing and used at 40
℃
, and those of the air switch are applicable to the one which also is used
at 40
℃
. If the actual installation conditions changes, please refer to the instructions of the power cord and the air
switch.