A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
92
The on spot connection should refer to the circuit diagram, which is stuck on the unit body.
The unit should be reliably earth, if it is improperly earthed that may cause electric shock or fire.
Air conditioner is the “I” class electric appliance, thus please do conduct reliable grounding measure.
The yellow-green two-color wiring of air conditioner is grounding wire and cannot be used for other purposes. It
cannot be cut off and be fixed by screw, otherwise it would cause electric shock.
The user must offer the reliable grounding terminal. Please don’t connect the grounding wire to the following
places:
Water pipe
①
;
Gas pipe
②
;
Blowing pipe
③
;
Other places that professional personnel consider them unreliable.
④
4.1.2 Connection between power cables and wiring terminals
Caution
Before installing the electrical equipment, please pay attention to the following matters which have been
specially pointed out by our designers:
①
Check to see if the power supply used conforms to the rated power supply specified on the nameplate.
②
The capacity of the power supply must be large enough. The section area of fitting line in the room shall be
larger than 2.5mm
2
.
③
The lines must be installed by professional personnel.
④
An electricity leakage protection switch and an air switch with gap between electrode heads larger than 3 mm
shall be installed in the fixed line.
1
)
Connection of single wire
①
Use wire stripper to strip the insulation layer (25mm long) from the end of the single wire.
②
Remove the screw at the terminal board of the air-conditioning unit.
③
User pliers to bend the end of the single wire so that a loop matching the screw size is formed.
④
Put the screw through the loop of the single wire and fix the loop at the terminal board.
2
)
Connection of multiple twisted wires
①
Use wire stripper to strip the insulation layer (10mm long) from the end of the multiple twisted wires.
②
Remove the screw at the terminal board of the air-conditioning unit.
③
Use crimping pliers to connect a terminal (matching the size of the screw) at the end of the multiple twisted
wires.
④
Put the screw through the terminal of the multiple twisted wires and fix the terminal at the terminal board.
Warning:
If the power supply flexible line or the signal line of the equipment is damaged, only use special flexible line to
replace it.
Before connecting lines, read the voltages of the relevant parts on the nameplate. Then carry out line