102. Receiving, Moving and Storing Systems and Batteries

102.1 Shipping Damage

LG125S,R and T inverter system batteries are shipped installed within the unit housing. The LG250S and LG250SI 

inverter system batteries are shipped separately from the inverter cabinet.

Carefully inspect all cartons upon receipt for evidence of shipping damage.

Notify carrier immediately of leaking or damaged cartons for possible concealed damage.

102.2 Temporary Storage of Units and Batteries

For temporary storage of LG inverter systems and batteries prior to installation, select a clean, cool, dry location with 

normal ventilation for human habitation and level floors.

Storage Temperature:

Store all batteries at 0° to +40° C (32° to +104° F). Batteries will have a longer shelf life if stored at 15° C (60° F). The 

LG electronics and battery cabinets may be stored at -20° to +60° C (-4° to +140° F).

IMPORTANT:

Lengthy storage of batteries will cause irreversible damage to the cells.

Failure to connect 

LG inverter system batteries to an energized charging circuit within 90 days from the date of ship-

ment will void the battery warranty.

DANGER: 

Explosive - Can Cause Blindness Or Other Severe Injuries

Every type of battery can produce hydrogen gas, even sealed, maintenance-free batteries. 

The gas is vented through 

the vent caps and into the air. Do not allow smoking, sparks, or flames in battery storage location because hydrogen is 

concentrated under the vent cap of each cell of the battery. Hydrogen is highly explosive, and is hard to detect because 

it is colorless, odorless, and lighter than air.

103. Installation Requirements

103.1 Operating Environment

Install the 

LG

 inverter system in a clean, cool, dry place with normal ventilation for human habitation and in such a loca-

tion to hamper vandalism but allow easy access for testing and maintenance.

Operating Temperature: 

LG inverter Systems are UL Listed for 20° to 30° C (+ 68° to +86° F) operation.

Battery performance and service life is maximized if the operating temperature is maintained at 25° C (77° F).

Temperature Effect On Battery Performance:

Batteries will be less efficient at temperatures below 20° C (68° F), and high temperatures will reduce battery life. Typi-

cally, at 35° C (95° F), battery life will be half of what it would be at normal temperature of 25° C (77° F). At 45° C (113° 

F), battery life will be one-fourth of normal.

Ventilation:

The air around the unit must be clean, dust-free, and free of corrosive chemicals or other contaminants. Do not place 

the LG inverter system or batteries in a sealed room or container.

CAUTION:  Never Install Batteries in A Sealed Room Or Enclosure

103.2 High Altitude Operation:

The maximum operating temperature drops 1° Celsius per 300 meters (2° F per 1000 feet) above sea level. Maximum 

elevation is 3000 meters (10,000 feet).

Summary of Contents for LG125R

Page 1: ...r 125VA 110W 250VA 220W Mini Inverter Power Systems Models LG125S Surface Mounted Version LG125R Recessed Wall Mounted Version LG125T Recessed Ceiling T Grid Mounted Version LG250S Surface Mounted Ver...

Page 2: ...uipment should be mounted in locations where it will not be readily subjected to tampering by unauthorized personnel 7 The use of accessory equipment not recommended by the manufacturer may cause an u...

Page 3: ...Output Connections 8 Wiring Diagram 1 120VAC Connections 9 Wiring Diagram 2 277VAC Connections 9 106 Battery Information 10 106 1 Tools 10 106 2 Battery Installation and Connections 10 Wiring Diagram...

Page 4: ...solator Standard battery Sealed lead calcium 10 year life Battery voltage 24 or 48 system dependent See Table 1 below Runtimes 90 minutes standard Operating temperature 20 C to 30 C 68 F to 86 F Relat...

Page 5: ...ent caps and into the air Do not allow smoking sparks or flames in battery storage location because hydrogen is concentrated under the vent cap of each cell of the battery Hydrogen is highly explosive...

Page 6: ...its and damage the equipment NOTE Consider unit knockout locations prior to mounting unit Allow room for easy routing of conduit to entry point 104 4 Surface Mount Models LG125S LG250S and LG250SI 1 R...

Page 7: ...ent of unit cover the LED indicator panel assembly position must be adjusted to sit flush against inside surface of cover after attachment This is accomplished using the 2 8 32 hex nuts on the indicat...

Page 8: ...Switch S2 is in the OFF position 2 Make sure the LG inverter system input and output voltages are correct for the particular application Remember that the LG system provides single phase power only 3...

Page 9: ...77V wiring Normally On and Normally Off Operation A combination of the operating modes described above See C in Wiring Diagram 1 for 120V wiring or G in Wiring Diagram 2 for 277V wiring Switched Load...

Page 10: ...void electric shock and burns caused by contacting battery terminals or shorting terminals during battery installation Do not touch uninsulated battery terminals 8 A qualified electrician who is famil...

Page 11: ...rrect polarity on the battery terminals Polarity markings may vary from battery to battery Battery Wiring Diagram 1 Battery Wiring Diagram 2 Battery Wiring Diagram 3 106 3 Battery Connection Voltage C...

Page 12: ...en to follow the steps below in their exact sequence Failure to do so may result in possible equipment failure CAUTION Familiarize yourself with the shut down procedure in Section 200 1 before proceed...

Page 13: ...s a service alert Refer to the INDICATION chart in Section 110 2 for details During loss of normal utility power the dual color LED will not be illuminated The AMBER INV ON LED indicator will be illum...

Page 14: ...ded if not routinely recharged NOTE To turn power back on follow the System Start up Procedure outlined in Section 108 Be sure to complete all of the steps to assure the unit will operate properly 200...

Page 15: ...stem and to maintain proper charger operation replace spent batteries only with cells having the same part number voltage and ampere hour rating as the original batteries 1 Follow the proper shut down...

Page 16: ...Hubbell Lighting Inc brand with representatives offices in principal cities throughout North America Copyright Hubbell Lighitng Inc All Rights Reserved Specifications subject to change without notice...

Reviews: