DTI Dyna Technology WINPOWER DE20I4 Installation And Operation Manual Download Page 9

2080-10

60708-151

7

5.  Be sure all connections are tight and coat the terminals and  

 

cable ends with dialectic grease. 

WARNING – 

The electrolyte is a diluted sulfuric acid that is 

harmful to the skin and eyes.  It is electrically conductive and 

corrosive.  The following precautions must always be taken:

*  Always wear full eye protection and protective clothing

*  Where electrolyte contacts the skin, wash off immediately    

 

with water.

*  If electrolyte contacts the eyes, flush thoroughly and 

 

immediately with water and seek immediate medical attention

*  Spilled electrolyte is to be washed down with an acid neutral 

 

izing agent.  A common practice is to use a solution of one   

 

pound of bicarbonate of soda (baking soda) to one gallon of  

 

water.  The bicarbonate of soda solution is to be added until  

 

the evidence of reaction, foaming, has ceased.  The resulting  

 

liquid is to be flushed with water and the area dried.

DANGER – Explosive Fire Risk

*  Never smoke when near batteries

*  Do not cause a flame or spark in the battery area

*   Always discharge static electricity from your body before    

 

touching batteries by first touching a grounded metal surface

SERVICING BATTERIES

Batteries used on these units may, over time, lose water.  This is 

especially true if you are using a trickle charger to maintain your 

battery.  When refilling the battery with water use only distilled 

water.  Tap water will shorten the service life of the battery.

Never fill the battery above the fill line.  Over filling above the 

upper level line may cause the electrolyte to overflow, resulting in 

corrosion to the engine or nearby parts.  Immediately wash off any 

spilled electrolyte following the procedure above.

NOTE:

 Always make sure that a new battery is fully charged 

before installing it on a generator set.  Failure to do so can cause 

damage to the engine control module in the generator set.

All connections must be clean and tight.  Check the electrolyte 

(fluid) in the battery periodically to be sure it is above the plates.  

Never allow the battery to remain in a discharged condition.

A.C. ELECTRICAL 

CONNECTIONS

NOTICE - CLASS 1 WIRING METHODS ARE TO BE USED FOR 

ALL FIELD WIRING CONNECTIONS TO TERMINALS OF A 

CLASS 2 CIRCUIT

Note: 

 This symbol             always indicates ground where shown.

All wiring must be completed in accordance with the Nation 

Electric Code as well as any state or local codes.

You must pay particular attention to wire size requirement  for 

the amperage of service you are dealing with.  The table below 

provides you guidance on wire sizing based on both wire type 

and amperage.   

Wire amperage’s have been derated for 40

C ambient temperatures operation. See page 8 for wiring 

schematic.

    *************

*****  WARNING  *****

    *************

A main line circuit breaker has been provided inside the 

generator housing. During all wiring installations make 

sure the breaker is in the OFF position and the generator 

operation switch is in the OFF position.  

Neutral Lugs

 -  DE20 has 100 amp neutral lugs. These lugs are 

isolated from ground and provided for you to connect your neutral 

wires to, from the transfer switch or load distribution center.  The 

lugs will accommodate #12 AWG to #1/0 Awg  and should be 

torqued to 50 in. lbs.  The DR30 and larger have 225 AMP neutral 

lugs and will accommodate #4 AWG to 300 MCM  and should be 

torqued to 250 in. lbs. The exception is the DE65 single phase 

unit which has a 400 amp neutral block.  The 400 amp terminal 

block lugs will handle wire sizes #1 AWG to 400 MCM and should 

be torqued to 300 in. lbs.

Generator Circuit Breaker, 

This circuit breaker provides overload 

protection for the generator.  Your power feeds from the load 

panel will connect to the open lugs on the circuit breaker.  The 

generator power feeds have already been wired into one set of 

lugs.  

The table below gives you the circuit breaker size,  lug wire sizes 

and torque specification.  (see the actual breaker for additional 

information  and restrictions)

kW 

Voltage 

PH  Amp  Wire Capability 

Lug Torque

20 

120/240 

85 

#12 AWG -2/0 AWG  50 in lbs 

20 

120/208 

70 

#12 AWG -2/0 AWG  50 in lbs 

20 

120/240 

60 

#12 AWG -2/0 AWG  50 in lbs

20 

277/480 

30 

#14 - #1/0 AWG 

80 in lbs

kW 

Voltage 

PH  Amp  Wire Capability 

Lug Torque

30 

120/240 

1  125 

#12 AWG -2/0 AWG  50 in lbs 

30 

120/208 

3  100 

#12 AWG -2/0 AWG  50 in lbs 

30 

120/240 

90 

#12 AWG -2/0 AWG  50 in lbs

30 

277/480 

45 

#14 - #1/0 AWG 

80 in lbs

kW 

Voltage 

PH  Amp  Wire Capability 

Lug Torque

45 

120/240 

1  175 

#4 AWG - 300 MCM  250 in lbs 

45 

120/208 

3  150 

#4 AWG - 300 MCM  250 in lbs

45 

120/240 

3  125 

#4 AWG - 300 MCM  250 in lbs

45 

277/480 

60 

#14 - #1/0 AWG 

80 in lbs

kW 

Voltage 

PH  Amp  Wire Capability 

Lug Torque

65 

120/240 

1  250 

#1 AWG - 600 MCM  375 in lbs

65 

120/208 

3  225 

#4 AWG - 300 MCM  250 in lbs

65 

120/240 

3  200 

#4 AWG - 300 MCM  250 in lbs

65 

277/480 

3  100 

#14 - #3/0 AWG 

120 in lbs

Summary of Contents for WINPOWER DE20I4

Page 1: ...INSTALLATION AND OPERATIONS MANUAL DE20I4 DE30I4 DE45I4 DE65I4 INSTALLATION AND OPERATIONS MANUAL MODELS DE20I4 DE30I4 DE45I4 DE65I4 DSE702 START MODULE AND MANUAL KEY START...

Page 2: ...L NUMBER________________________ M Spec ______________________________ PURCHASE DATE_______________________ DEALER_______________________________ TABLE OF CONTENTS INTRODUCTION i GUIDE TO PRODUCT SAFE...

Page 3: ...into the earth 2 FIRE HAZARD Diesel fuel presents a hazard of possible explosion and or fire a Do not smoke or use open flame near the generator set b Keep a fire extinguisher nearby and know its prop...

Page 4: ...Muffler Standard Stop System Key Emergency Fuel Consumption full Load 2 6 Gal hour Owner Must Provide Fuel ASTM D 975 1D or 2D EN590 or equivalent See engine manual for additional fuel types specifica...

Page 5: ...nd replacement parts Be sure to have the main WINPOWER unit data plate information recorded inside the front cover of this manual for future reference and for identification whenever requesting field...

Page 6: ...hysical damage locate and check the following items packed with the unit a Owner s operators manual b Engine manufacturer s instruction manual c Battery hold down brackets hardware d Unit components o...

Page 7: ...should be 1 1 2 time as large as the area of the radiator face to prevent back pressure In addition to a hot air discharge you must plan for a fresh air intake opposite the radiator discharge These fr...

Page 8: ...tive ground system If you are using the truck batteries to start these units you may have to disable the charging system to keep it from interfering with the vehicle charging system Installation and s...

Page 9: ...leted in accordance with the Nation Electric Code as well as any state or local codes You must pay particular attention to wire size requirement for the amperage of service you are dealing with The ta...

Page 10: ...60708 151 2080 10 CONTROL BOX AC WIRING WARNING THESE GENERATORS ARE WIRED WITH A FLOATING NEUTRAL...

Page 11: ...h to The lugs on the 65 kW will handle wire sizes 6 AWG to 300 MCM and should be torqued to 250 in lbs The lugs on the 20 through 45 kW will accommodate 10 AWG to 2 0 AWG and should be torqued to 200...

Page 12: ...detects that the engine coolant temperature has exceeded the limit the coolant temperature switch after the Safety On timer has expired and a shutdown is initiated NOTE All warnings are reset but tur...

Page 13: ...ours of engine operation D 25 AMP FUSE This fuse protect all the DC wiring in the engine control panel and on the engine If this Fuse if blown nothing will work on the engine E SAFETY LATCHING RELAY T...

Page 14: ...nit stopped with the relay button popped out it could have been caused by either low oil pressure or high water temperature TROUBLESHOOTING TABLES ENGINE WILL NOT CRANK WITH GENERATOR RUN PUSH BUTTON...

Page 15: ...2080 10 60708 151 13 DE30 OUTLINE DRAWING DE20 OUTLINE DRAWING...

Page 16: ...60708 151 2080 10 14 DE45 DE60 OUTLINE DRAWING...

Page 17: ...2080 10 60708 151 15 DE20 DE30 DC SCHEMATIC FOR DSE702...

Page 18: ...60708 151 2080 10 16 DE45 DE65 DC SCHEMATIC FOR DSE702...

Page 19: ...2080 10 60708 151 17 START CONTROL PANEL ENGINE WIRING HARNESS DE20 DE30 KEY START SCHMATIC...

Page 20: ...60708 151 2080 10 18 START CONTROL PANEL ENGINE WIRING HARNESS DE45 DE65 KEY START SCHMATIC...

Page 21: ...2080 10 60708 151 19 THREE PHASE AC WIRING HIGH AND LOW WYE...

Page 22: ...60708 151 2080 10 20 THREE PHASE AC WIRING DELTA SINGLE PHASE AC WIRING...

Page 23: ...of merchantability and fitness for a particular purpose are limited to 12 months or 1000 hours which ever occurs first from date of purchase In no event is WINPOWER liable for incidental or consequent...

Page 24: ...225 S Cordova ave Le Center MN 56057 507 357 6831 www winpowerinc com 60708 151 2080 10...