DTI Dyna Technology WINPOWER DE20I4 Installation And Operation Manual Download Page 4

60708-151

2080-10

2

TESTING POLICY:

Before any generator is shipped from the factory, it is fully 

checked for performance.  The generator is loaded to its 

full capacity, and the voltage, current, and frequency are 

carefully checked. 

Rated outpdut of the generators is based on engineering 

tests of typical units, and is subject to, and limited by, the 

temperature, altitude, fuel, and other conditions specified by 

the manufacturer of the applicable engines.

SPECIFICATIONS 

MODEL 

DE20I4-A  DE20I4-D  DE20I4-J  DE20I4-L

Generator 

Wattage 

20000 

20000 

20000 

20000

Volts 

120/240 

120/208 

120/240 

277/480

Phase 

single 

three 

three 

three

PF 

1.0 

.80 

.80 

.80 

AMPs  

83.0 

69.5 

60.2 

30.1

Hertz 

60 

60 

60 

60   

Engine

 

Model 

Isuzu 4LE1

Starting System    

12 Volt Manual Start

Muffler 

Standard

Stop System 

Key/Emergency 

Fuel Consumption (full Load) 1.8 Gal/hour 

Owner Must Provide 

Fuel 

ASTM D-975 - 1D or  2D

 

EN590 or equivalent

 

See engine manual for additional

 

fuel types & specification

Oil Type 

10W-30 CC/CD  

 

See engine manual for additional oil information. 

Oil Capacity 

8.6 Quarts

Cooling System 

50/50 Mix

MODEL 

DE30I4-A  DE30I4-D  DE30I4-J 

DE30I4-L

Generator 

Wattage 

30000 

30000 

30000 

30000

Volts 

120/240 

120/208 

120/240 

277/480

Phase 

single 

three 

three 

three

PF 

1.0 

.80 

.80 

.80 

AMPs  

125 

104 

90 

45

Hertz 

60 

60 

60 

60 

Engine

 

Model 

Isuzu 4LE TurboCharged

Starting System    

12 Volt Manual Start

Muffler 

Standard

Stop System 

Key/Emergency 

Fuel Consumption  (full Load) 

2.6 Gal/hour 

Owner Must Provide 

Fuel 

ASTM D-975 - 1D or  2D

 

EN590 or equivalent

 

See engine manual for additional

 

fuel types & specification

Oil Type 

10W-30 CC/CD  

 

See engine manual for additional oil information. 

Oil Capacity 

8.6 Quarts

Cooling System 

50/50 Mix

MODEL DE45I4-A  DE45I4-D 

DE45I4-J  DE45I4-L

Generator 

Wattage 

45000 

45000 

45000 

45000

Volts 

120/240 

120/208 

120/240 

277/480

Phase 

single 

three 

three 

three

PF 

1.0 

.80 

.80 

.80 

AMPs  

187 

156 

135 

68

Hertz 

60 

60  60 

60 

 

 

Engine

 

Model 

Iveco N45SM1

Starting System    

12 Volt Manual Start

Muffler 

Standard

Stop System 

Key/Emergency 

Fuel Consumption  (full Load) 

4.09 Gal/hour 

 

Owner Must Provide 

Fuel 

ASTM D-975 - 1D or  2D

 

EN590 or equivalent

 

See engine manual for additional

 

fuel types & specification

Oil Type 

10W-30 CF-CH4

 

See engine manual for additional oil information. 

Oil Capacity 

13.5 Quarts

Cooling System 

50/50 Mix

MODEL 

DE65I4-A  DE65I4-D 

DE65I4-J  DE65I4-L

Generator 

Wattage 

65000 

65000 

65000 

65000

Volts 

120/240 

120/208 

120/240 

277/480

Phase 

single 

three 

three 

three

PF 

1.0 

.80 

.80 

.80 

AMPs  

271 

226 

195 

98

Hertz 

60 

60 

60 

60   

Engine

 

Model 

Iveco N45SM2 TurboCharged

Starting System    

12 Volt Manual Start

Muffler 

Standard

Stop System 

Key/Emergency 

Fuel Consumption  (full Load) 

4.57 Gal/hour 

 

Owner Must Provide 

Fuel 

ASTM D-975 - 1D or  2D

 

EN590 or equivalent

 

See engine manual for additional 

 

fuel types & specification

Oil Type 

10W-30 CF-CH4  

 

See engine manual for additional oil information. 

Oil Capacity 

13.5 Quarts

Cooling System 

50/50 Mix 

Summary of Contents for WINPOWER DE20I4

Page 1: ...INSTALLATION AND OPERATIONS MANUAL DE20I4 DE30I4 DE45I4 DE65I4 INSTALLATION AND OPERATIONS MANUAL MODELS DE20I4 DE30I4 DE45I4 DE65I4 DSE702 START MODULE AND MANUAL KEY START...

Page 2: ...L NUMBER________________________ M Spec ______________________________ PURCHASE DATE_______________________ DEALER_______________________________ TABLE OF CONTENTS INTRODUCTION i GUIDE TO PRODUCT SAFE...

Page 3: ...into the earth 2 FIRE HAZARD Diesel fuel presents a hazard of possible explosion and or fire a Do not smoke or use open flame near the generator set b Keep a fire extinguisher nearby and know its prop...

Page 4: ...Muffler Standard Stop System Key Emergency Fuel Consumption full Load 2 6 Gal hour Owner Must Provide Fuel ASTM D 975 1D or 2D EN590 or equivalent See engine manual for additional fuel types specifica...

Page 5: ...nd replacement parts Be sure to have the main WINPOWER unit data plate information recorded inside the front cover of this manual for future reference and for identification whenever requesting field...

Page 6: ...hysical damage locate and check the following items packed with the unit a Owner s operators manual b Engine manufacturer s instruction manual c Battery hold down brackets hardware d Unit components o...

Page 7: ...should be 1 1 2 time as large as the area of the radiator face to prevent back pressure In addition to a hot air discharge you must plan for a fresh air intake opposite the radiator discharge These fr...

Page 8: ...tive ground system If you are using the truck batteries to start these units you may have to disable the charging system to keep it from interfering with the vehicle charging system Installation and s...

Page 9: ...leted in accordance with the Nation Electric Code as well as any state or local codes You must pay particular attention to wire size requirement for the amperage of service you are dealing with The ta...

Page 10: ...60708 151 2080 10 CONTROL BOX AC WIRING WARNING THESE GENERATORS ARE WIRED WITH A FLOATING NEUTRAL...

Page 11: ...h to The lugs on the 65 kW will handle wire sizes 6 AWG to 300 MCM and should be torqued to 250 in lbs The lugs on the 20 through 45 kW will accommodate 10 AWG to 2 0 AWG and should be torqued to 200...

Page 12: ...detects that the engine coolant temperature has exceeded the limit the coolant temperature switch after the Safety On timer has expired and a shutdown is initiated NOTE All warnings are reset but tur...

Page 13: ...ours of engine operation D 25 AMP FUSE This fuse protect all the DC wiring in the engine control panel and on the engine If this Fuse if blown nothing will work on the engine E SAFETY LATCHING RELAY T...

Page 14: ...nit stopped with the relay button popped out it could have been caused by either low oil pressure or high water temperature TROUBLESHOOTING TABLES ENGINE WILL NOT CRANK WITH GENERATOR RUN PUSH BUTTON...

Page 15: ...2080 10 60708 151 13 DE30 OUTLINE DRAWING DE20 OUTLINE DRAWING...

Page 16: ...60708 151 2080 10 14 DE45 DE60 OUTLINE DRAWING...

Page 17: ...2080 10 60708 151 15 DE20 DE30 DC SCHEMATIC FOR DSE702...

Page 18: ...60708 151 2080 10 16 DE45 DE65 DC SCHEMATIC FOR DSE702...

Page 19: ...2080 10 60708 151 17 START CONTROL PANEL ENGINE WIRING HARNESS DE20 DE30 KEY START SCHMATIC...

Page 20: ...60708 151 2080 10 18 START CONTROL PANEL ENGINE WIRING HARNESS DE45 DE65 KEY START SCHMATIC...

Page 21: ...2080 10 60708 151 19 THREE PHASE AC WIRING HIGH AND LOW WYE...

Page 22: ...60708 151 2080 10 20 THREE PHASE AC WIRING DELTA SINGLE PHASE AC WIRING...

Page 23: ...of merchantability and fitness for a particular purpose are limited to 12 months or 1000 hours which ever occurs first from date of purchase In no event is WINPOWER liable for incidental or consequent...

Page 24: ...225 S Cordova ave Le Center MN 56057 507 357 6831 www winpowerinc com 60708 151 2080 10...

Reviews: