1. Select programming mode
To enter programming mode: Change DIL switch 1
(S4) to ON position.
Back to normal mode: Change DIL switch 1 (S4) to
OFF position.
2. Navigating the table
STOP push
-
button is used to navigate between pa-
rameter number and parameter value.
OPEN and CLOSE push
-
buttons is used to select pa-
rameter number or change parameter value.
Active digits will be flashing.
Some of the parameters have an extra step when
pressing the stop push
-
button. For example when the
door needs to run in programming stage. Display will
show
”
RUN
”.
3. Parameter explanation
5. INITIAL OPERATION
Before initial operation and at regular intervals of no
more than one year, power
-
operated windows, doors
and gates must be inspected by a qualified person
(whereby written inspection records must be kept).
After setting the system in operation, the operator of
the door system, or the operator
’
s representatives,
must be instructed in the operation of the system.
Make sure before installation that the direction of rota-
tion of the gear motor is correct and that all protective
devices are functioning.
5.1 Electrical installation
5.2 HOW TO program
The door will always run in hold
-
to
-
run mode when
programming. Program the control by opening the en-
closure. Find OPEN
-
CLOSE
-
STOP push
-
buttons
and a 4 pole DIL switch on the PCB (S4).
NOTICE !
To avoid damaging the device, the following must be
ensured:
•
The cable types and cross
-
sections are to be chosen
according to the regulations.
•
The rated currents and the connection type must
match those on the motor type plate.
•
The on site fuse must comply with the specifications.
DANGER !
Life
-
threatening danger due to electric shock!
It is vital that you disconnect the operator system from
the power supply before commencing cabling work.
Take measures to ensure that the power supply re-
mains disconnected for the duration of the work.
NOTICE !
•
The main power supply must be in the range of max.
+/
-
10% of the control unit
’
s mains supply.
•
Be sure not to overload the gear motor in accord-
ance with the electrical data on the type plate.
•
Temperature control is necessary when using the
control outside the temperature range
-
10
-
+ 50°C.
•
The control unit must not be used in environments
with risk of condensation.
Parameter value.
Parameter number.