Front Panel Configuration
Part No. 057-129 DSE871x mono remote display ISSUE 2.1 21/09/2010 ADM
61
9.1.2 ADJUSTABLE PARAMETERS
Front Panel Configuration Editor. For descriptions of the parameters, you are referred to The DSE87xx series
Configuration Suite Manual, DSE Part 057-119.
Section
Parameter as shown on display
Values
Display
Contrast
53%
Language
English, others.
Current Date and Time
hh:mm
Timers
LCD Page Timer
5m
Scroll Delay
2s
Engine Pre Heat Timer
0s
Engine Crank Duration
10s
Engine Crank Rest Time
10s
Engine Safety On Delay
10s
Engine Smoke Limiting
0s
Engine Smoke Limiting Off
0s
Engine Warm Up Time
1s
Engine Cool Down Time
1m
Engine Speed Overshoot Delay
0s
Engine Failed To Stop
30s
Battery Under Voltage Warning Delay
1m
Battery Over Voltage Warning Delay
1m
Return Delay
30s
Generator Transient Delay
0s
Generator
Under Voltage Shutdown
184v
Under Voltage Pre-Alarm
196v
Nominal Voltage
230v
Over Voltage Pre-Alarm
265v
Over Voltage Shutdown
277v
Under Frequency Shutdown
40Hz
Under Frequency Pre-Alarm
42Hz
Nominal frequency
200%
Over Frequency Pre-Alarm
50Hz
Over Frequency Shutdown
54Hz
Full Load Rating
57Hz
Delayed Over current
500A
Delayed Over Current
Active
AC System
100%
CT Primary
3 Phase 4 Wire
CT Secondary
600A
Short Circuit Trip
5A
Earth CT Primary
500A
Earth Fault Trip
Inactive
Earth Fault Trip
10%
Transient Delay
0s
Gen Reverse Power Delay
2s
Full kW rating
245kW
Full kVAr rating
258kVAr
Load Ramp Rate
3%
Load Level For More Sets
80%
Load Level For Less Sets
70%
Load Demand Priority
1
Gen Reverse Power
35kW
Gen Over Current
0%
Insufficient Capacity Delay
1s
Insufficient Capacity Action
None
Reactive Load CTL Mode VAr Share
None
Load Parallel Power
172kW When In Mains Parallel Mode
Load Power factor
0% When In Mains Parallel Mode
Engine
Oil Pressure Low shutdown
1.03bar
Oil Pressure Low Pre-Alarm
1.17bar
Coolant Temp High Pre-Alarm
90ºC
Coolant Temp High Electrical Trip
92ºC
Coolant Temp High Shutdown
95ºC
Start Delay Off load
5s
Start Delay on load
5s
Start Delay mains fail
0s
Start Delay Telemetry
5s
Pre Heat Timer
0s
Crank Duration
10s
Crank rest Time
10s
Safety On Delay
10s
Smoke Limited
0s
Smoke limiting off
0s
Warm Up Time
1s
Cool Down Time
1m
Speed Overshoot Delay
0s
Speed Overshoot
0%
Fail To Stop Delay
30s
Battery Under Volts Warning
Active
Battery Under Volts Warning Delay
1m
Battery Under Volts Warning
19v
Battery Over Volts Warning
Active
Battery Over Volts Warning Delay
1m
Battery Over Volts Warning
30v
Charge Alternator Failure Warning
Active
Charge Alternator Failure Warning
6.0v
Charge Alternator Warning Delay
5s
Charge Alternator Failure Shutdown
Active
Charge Alternator Failure Shutdown
4.0
Charge Alternator Shutdown Delay
5s
Droop %
Active, Inactive. Electronic engines only when droop is
enabled.
Scheduler
Scheduler
Active, Inactive
Schedule On Load
Active , Inactive (Only Available When Scheduler Is Active)
Schedule Period
Weekly, Monthly (Only Available When Scheduler Is Active)
Schedule Time & Date Selection (1-16)
Press
to begin editing then press
or
when
selecting the different parameters in the scheduler.