Protections
48
Part No. 057-129 DSE871x mono remote display ISSUE 2.1 21/09/2010 ADM
6.3 WARNINGS
Warnings are non-critical alarm conditions and do not affect the operation of the generator system, they serve to
draw the operators attention to an undesirable condition.
Example
Alarm 1/1
Charge Failure
Warning
In the event of an alarm the LCD will jump to the alarms page, and scroll through all active warnings and
shutdowns.
By default, warning alarms are self-resetting when the fault condition is removed. However enabling ‘all warnings
are latched’ will cause warning alarms to latch until reset manually. This is enabled using the DSE87xx series
configuration suite in conjunction with a compatible PC.
If the module is configured for, CAN and receives an “error” message from the engine control unit, ‘Can ECU
Warning” is shown on the module’s display and a warning alarm is generated.
6.4 HIGH CURRENT WARNING ALARM
GENERATOR HIGH CURRENT, if the module detects a generator output current in excess of the pre-set trip a
warning alarm initiates. The module shows Alarm Warning High Current. If this high current condition continues for
an excess period, then the alarm escalates to a shutdown condition. For further details of the high current alarm,
please see High Current Shutdown Alarm.
By default, High Current Warning Alarm is self-resetting when the overcurrent condition is removed. However
enabling ‘all warnings are latched’ will cause the alarm to latch until reset manually. This is enabled using the
DSE87xx series configuration suite in conjunction with a compatible PC.