Controls and Indications
Part No. 057-129 DSE871x mono remote display ISSUE 2.1 21/09/2010 ADM
35
Transfer to generator (DSE8710/8711 only)
Allows the operator to transfer the load to the generator, synchronising first if required. (when in
Manual mode only)
Open generator (DSE8710/8711 only)
Allows the operator to open the generator breaker (when in Manual mode only)
Close mains (DSE8760/8716 only)
This push button is used to control the closure of the mains load switching device and has two modes
of operation :
1. Synchronising is NOT enabled. Pressing this button when the mains is available off load and in
MANUAL mode, the bus load switch is opened and the mains load switch is closed. Further
presses of this button will have no effect.
2. Synchronising is enabled. Pressing this button when the mains is available and in MANUAL
mode, the 8760 controller, will volts match and synchronise with the Bus. The mains load switch
is then closed in parallel with the Bus.
NOTE:
NOTE:
NOTE:
NOTE:---- This button is only active in MANUAL mode.
This button is only active in MANUAL mode.
This button is only active in MANUAL mode.
This button is only active in MANUAL mode.
NOTE:
NOTE:
NOTE:
NOTE:---- If the bus is live when the manual button is pressed, synchronising will take
If the bus is live when the manual button is pressed, synchronising will take
If the bus is live when the manual button is pressed, synchronising will take
If the bus is live when the manual button is pressed, synchronising will take
place before the load
place before the load
place before the load
place before the load switch is closed.
switch is closed.
switch is closed.
switch is closed.
Close bus (DSE8760/8716 only)
This push button is used to control the closure of the bus load switching device and has two modes of
operation :
3. Synchronising is NOT enabled. Pressing this button when the bus is off load and in MANUAL
mode, the mains load switch is opened and the bus load switch is closed. Further presses of this
button will have no effect.
4. Synchronising is enabled. Pressing this button when the bus is live and in MANUAL mode, the
8760 controller, will volts match and synchronise with the Mains. The bus load switch is then
closed in parallel with the mains.
NOTE:
NOTE:
NOTE:
NOTE:---- This button is only active in MANUAL mode.
This button is only active in MANUAL mode.
This button is only active in MANUAL mode.
This button is only active in MANUAL mode.
NOTE:
NOTE:
NOTE:
NOTE:---- If the bus is live when the manual button is pressed, synchronising will tak
If the bus is live when the manual button is pressed, synchronising will tak
If the bus is live when the manual button is pressed, synchronising will tak
If the bus is live when the manual button is pressed, synchronising will take
e
e
e
place before the load switch is closed.
place before the load switch is closed.
place before the load switch is closed.
place before the load switch is closed.
Menu navigation
Used for navigating the instrumentation, event log and configuration screens.
For further details, please see the more detailed description of these items elsewhere in this manual.