Description Of Controls
64
5.1 CONTROL PUSH-BUTTONS
NOTE: For further details, see section entitled ‘Operation’ elsewhere in this manual.
Icon
Description
Stop / Reset
Mode
This button places the module into its
Stop/Reset Mode
.
This clears any
alarm conditions for which the triggering criteria have been removed. If the
generator is running on load and the module is put into
Stop/Reset Mode
, the
module automatically opens the generator bus breaker
(‘
Close Bus
’ become
inactive)
and instructs the DSE8x10 module to enter the return delay. Should any
form of
Remote Start Signal
be present while operating in this mode, a start
request to the DSE8x10 module over the MSC Link does not occur.
Manual Mode
This button places the module into its
Manual
Mode
.
Once in
Manual
Mode
,
the module responds to the
Start
button to send a start
request to the DSE8x10 module over the MSC Link. The module monitors the
MSC Link for feedback from the DSE8x10 module to confirm the generator bus is
available.
If the generator bus is running off-load in the
Manual
Mode
and a
Start
Signal
becomes active, the module automatically instructs the changeover device
to place the generator bus on load
(‘
Close Bus
’
becomes active)
, synchronising to
the Mains if required
.
Upon removal of the
Start On Load Signal
, the generator
bus remains on load until either the
Stop/Reset Mode
or
Auto Mode
is
selected.
Also in
Manual
Mode
,
the module responds to the
Transfer to Mains
and
Transfer to Generator Bus
buttons after the generator bus is available.
Synchronising occurs automatically if required.
Test Mode
This button places the module into its
Test
Mode
.
Once in
Test
Mode
,
the module responds to the
Start
button to send a start request to the
DSE8x10 module over the MSC Link. The module monitors the MSC Link for
feedback from the DSE8x10 module to confirm the generator bus is available.
Once the generator bus is available, it is automatically placed on load
(‘
Close
Bus
’
becomes active)
, synchronising to the Mains if required. Depending upon
module configuration, the generator bus remains in constant parallel with the
Mains or proceeds to run in island operation
(‘
Close Mains
’
becomes inactive)
.
The generator bus remains on load until either the
Stop/Reset Mode
or
Auto Mode
is selected.
Summary of Contents for DSE8661
Page 11: ...Specification 11...
Page 54: ...Installation 54 4 2 2 2 MODULE INTER CONNECTION DSENET TO RS485...
Page 55: ...Installation 55 4 2 3 ALTERNATE TOPOLOGIES 4 2 3 1 SINGLE PHASE 2 WIRE...
Page 56: ...Installation 56 4 2 3 2 2 PHASE L1 L2 3 WIRE DELTA...
Page 57: ...Installation 57 4 2 3 3 2 PHASE L1 L3 3 WIRE DELTA...
Page 58: ...Installation 58 4 2 3 4 3 PHASE 3 WIRE DELTA...