The PC1550 Version 4.0 Software incorporates several new features and changes. The most impoartant additions are features
designed to prevent false alarms caused by user error, and to provide full support for the LINKS1000 Cellular Alarm Transmitter.

False Alarm Reduction Features

The following features have been added to reduce the number of false alarms caused by user error.

Section [17] System Times

System times now allow more than 4 minutes for the Entry or Exit delay to allow users more time to enter or leave the premises. The
default setting for the Exit Delay is now 120 seconds.

Section [24] Programmable Output Options

Two new options - 0A and 0B - will activate the PGM Output for the Entry Delay and Exit Delay respectively. These new options may
be used to activate warning devices to warn occupants on the premises that the security system is being armed or disarmed.

Section [34] 6th System Option Code

The new 6th System Option Code adds 5 new false alarm prevention features. Each feature is enabled by turning it’s Zone Light ON.

Zone Light 1

Audible Exit Delay with Urgency

The Keypad will sound a pulsing tone during the Exit Delay. The pulsing tone
will quicken during the last 10 seconds of the Exit Delay to warn the delay
is about to expire.

Zone Light 2

Bell Squawk During Exit Delay

The bell/siren will squawk during the Exit Delay. If Zone Light 1 is on, the
bell/siren squawk will quicken during the last 10 seconds of the Exit Delay.

Zone Light 3

Audible Exit Fault

When enabled, the bell/siren will sound with a steady tone to warn the user
that the system has been armed with a Delay Zone left open.

Zone Light 4

Urgency Applied to Entry Delay

The Keypad sounder will sound a quick pulsing tone during the last 10
seconds of the Entry Delay to warn that the Entry Delay is about to expire.

Zone Light 5

Bell Squawk During Entry Delay

The bell/siren will squawk during the Entry Delay. If Zone Light 4 is on, the
bell/siren squawk will quicken during the last 10 seconds of the Entry Delay.

LINKS1000 Support

The following items have been added to provide support for the LINKS1000 Cellular Alarm Communicator

Programming Section [24] Programmable Output Options

Program this Section as “0C” to enable LINKS1000 operation.

Programming Section [35] LINKS1000 Test Transmission Code

Program a 2-digit code in this section to be reported during cellular communication test transmissions.

Other Programming Changes and Additions

Programming Section [17] System Times

All System Times are now programmed with 3 digits.

Programming Section [32] 5th System Option Code

Zone Light 3 is now ON in the default setting, meaning that Home-Away Zones will have an Entry Delay.

Zone Light 6 is now ON in the default setting, meaning that all zones except for Fire Zones will be bypassed for 60 seconds when power
is applied to the control panel

Programming Section [36] Keypad Lockout Control

This new Section allows the installer to determine how many invalid codes (from 00 to 99) may be entered before the keypad is locked
out. Section [36] also determines how long the keypad will remain locked out (00 to 99 minutes) before resuming normal operation.
When the keypad is locked out, the system will not accept attempts to key in an Access Code, although the [F], [A], and [P] keys will
still function.

New Downloading Software

Downloading Software DLS-1 Version 5.3C and later must be used to upload and download with the new PC1550 v4.0 Software. Do
not attempt to perform downloading/uploading functions with the DLS-1 v5.2C or earlier software.

PC1550 v4.0 Notice of Software Release

©

 

1996 Digital Security Controls Ltd.

1645 Flint Road, Downsview, Ontario, Canada M3J 2J6

Printed in Canada     29000581 R4

Summary of Contents for PC1550

Page 1: ...9 04 2nd Account Code 9 05 to 10 Reporting Codes 9 05 Zone Alarm Reporting Codes 9 06 Zone Restoral Reporting Codes 9 07 Closing Arming Reporting Codes Partial Closing Reporting Code 9 08 Opening Disa...

Page 2: ...peration Download Upload capability Programmable auto downloading Swinger shutdown Transmission delay Six access codes Master key code All zones programmable as fire zones Programmable test transmissi...

Page 3: ...witched AC source and close to the telephone line connection Remove the printed circuit board the mounting hardware and the keypad from the cardboard retainer inside the cabinet Before attaching the c...

Page 4: ...fire generally rises to the ceiling spreads out across the ceiling surface and begins to bank down from the across the ceiling surface and begins to bank down from the across the ceiling surface and...

Page 5: ...before going to bed and is useful for users who have a keypad outside areas protected by the interior zones Arming Without Entry Delay To eliminate Entry Delay arm the system using 9 access code An ex...

Page 6: ...aster Code The installer may choose to not allow the user to program the Master Code section 13 option 2 The 6th code may be changed from a regular code into a One time Use code or Maid s Code section...

Page 7: ...ammable section 14 option 5 for feedback 3 beeps or silent no buzzer feedback If programmed for audible the buzzer will sound once the key input is accepted keep time When the panel is powered up the...

Page 8: ...mode For2 digitpairs bothdigitsmustbeprogrammed before pressing the key Only the data entered before pressing the key will be changed in the EEPROM Program Data Review Enter the section you wish to pr...

Page 9: ...2 digit code 31 TRANSMISSION SENT 1234 31 3 1 FORMAT Extended reporting requires 3 digit Account Code in section 02 or 04 i e Enter 1230 for code 123 Format Code 8 9 A B C depending on receiver type i...

Page 10: ...ny loop programmed for fire the Trouble light will come ON and the keypad sounder will beep every 10 seconds Thekeypadtroublebuzzerwillsoundandthe Trouble light will come ON regardless of whether the...

Page 11: ...r zone definitions 2 Exit delay time 001 to 255 seconds This value determines the standard Exit Delay time The factory default exit time is 120 seconds For zone definitions see Section 11 3 Bell cut o...

Page 12: ...the type of format which will be sent to each of the two telephone numbers programmed in section 01 and 03 For each telephone number enter one digit from the list below See the HEX data programming se...

Page 13: ...he Exit Delay This option may be used to provide lighting in the exit area or to activate a device when the Exit Delay begins 0C LINKS1000 Interface This option configures the system for use with the...

Page 14: ...Squawk during Entry Delay OFF No Bell Squawk during Entry Delay 6 ON F Key disabled OFF F Key enabled Factory default When Light 3 is ON Audible Exit Fault When the system is armed and a Standard Del...

Page 15: ...__________________________________ ZONES Zone Type Protected Area 1 _____________________________ __________________________________________________________________ 2 _____________________________ ___...

Page 16: ...Closing Arming Reporting Codes Partial Closing Reporting Code Page 9 Access Code 1 Access Code 4 Access Code 2 Access Code 5 Access Code 3 Access Code 6 Partial Closing Code 08 Opening Disarming Repo...

Page 17: ...sistor loops ON Zone Light 6 Keypad P anic audible bell Keypad P anic silent bell 13 2nd System Option Code Page 11 Default Zone Light ON Zone Light OFF ON Zone Light 1 Call 1st phone only Backup to 2...

Page 18: ...Light 6 17 System Times Page 11 Default Default 0 3 0 Entry Delay seconds 0 3 0 AC fail transmission delay minutes 1 2 0 Exit Delay seconds 0 5 0 Slow loop response time x 10 ms 0 0 4 Bell Cut off mi...

Page 19: ...econds 7 08 Strobe Output latched alarm output 03 Utility Output Any Access Code 5 seconds 7 09 Failure to Communicate Output follows trouble 4 04 5 Second Reset Pulse 7 0A PGM ON during Entry Delay 0...

Page 20: ...liary delay Auxiliary delay normal ON Zone Light 6 60 s bypass on power up Zones active on power up 33 Answering Machine Double Call Timer Page 14 Default 0 6 0 Valid entries are 001 to 249 34 6th Sys...

Page 21: ...ay consist of any combination of devices subject only to the requirement that the total of the Load Numbers of all the devices does not exceed 100 The Load Number of this unit is 2 AVIS L tiquette de...

Page 22: ...ds of the Entry Delay to warn that the Entry Delay is about to expire Zone Light 5 Bell Squawk During Entry Delay The bell siren will squawk during the Entry Delay If Zone Light 4 is on the bell siren...