Communication Formats
This section determines the communication format to be used when transmitting information to the two
telephone numbers programmed in Sections
and
For each telephone number, enter one digit from
the list below. Refer to “HEX Data Programming” for instructions on entering HEX numbers.
The format for each phone number is determined by the type of receiver being called. Enter the format number
for the 1st telephone number first. Program a format for both telephone numbers even if the first phone number
is the only one being used.
Name
Handshake
[0]
Silent Knight Ademco Slow 10 bps
1400 Hz
Sescoa, Frankline, DCI, Vertex 20 bps
2300 Hz
Silent Knight Fast 20 bps
1400 Hz
Radionics
400
Formats
and 412 non-extended formats
and
and
non extended formats
non extended formats
Radionics
Do Not Use
Do Not Use
Do
Not Use
400 Hz
non-extended with parity format
Silent Knight Ademco Slow 10 bps
1400 Hz
extended format
Sescoa, Franklin, DCI, Vertex 20 bps
2300 Hz
extended format
[A] Silent Knight Fast 20 bps
[B] Radionics
[C] Radionics
1400 Hz
2300 1400
2300 1400
extended format
extended format
extended with parity format
[D] Do Not Use
Do Not Use
Do Not Use
l
See Section
for Radionics handshake option.
Communications Compatibility
All communication formats described here are compatible with the Silent Knight SK9000 and Ademco Model
685 receivers. For UL installations, ensure that the control unit is reporting to one of these receivers.
BPS and 20 BPS Formats
10
BPS is the standard slow format used on Silent Knight Ademco receivers. DATA = 1900 Hz;
=
1400 Hz; SPEED = baud
20 BPS is the standard fast format used on the DCI Franklin Sescoa and Vertex receivers. DATA = 1800 Hz;
2300 Hz; SPEED = 20 baud
firealarmresources.com