6.1 Device Fail Time
When supervision of a wireless detector is turned ON, the panel will show a trouble if a
wireless zone stops working or is removed from the system. When supervision is turned
OFF, the panel will not show a trouble.
NOTE: Wireless keys are NOT supervised.
A
zone supervisory is a test transmission that each wireless zone sends to the RF4164-433
receiver. When the RF4164-433 module receives the supervisory transmission from the zone,
the RF4164-433 module will transmit this information to the control panel.
If the control panel does not get a supervisory transmission from a zone within the
Device Fail time, the zone will be considered “missing”, causing a Device Fault.
The next supervisory transmission that the RF4164-433 receives from the “missing”
zone will restore communication with that zone and restore the Zone Supervisory Fault.
The Device Fail timer will also be reset.
Change the Supervision Option
1. At an LCD keypad, enter [
✱
][8][Installer’s Code].
2. Enter Ref #[001306] to go to the
Supv Window
section.
3. Devices are listed by zone number in the order in which they were enrolled.
Scroll to each device. Press [
✱
] to turn the supervision option ON or OFF for that
device.
4. To exit, press [#].
Change the Device Fail Time
The default amount of time is 3 hours.
NOTE: This must be changed to 24 hours for systems using North American devices.
1. At an LCD keypad, enter [
✱
][8][Installer’s Code].
2. Enter Ref #[001307] to go to the
Device Fail Time
section.
3. Enter the time as [HHMM] (valid entries 01:00 - 23:59).
4. To exit, press [#].
6.2 Trouble Conditions
The PC4020 always watches for possible trouble conditions. If a trouble condition
occurs, the LCD keypad “Trouble” light will turn on and the keypad will beep. Press
[
✱
][2] to display the trouble conditions.
S E C T I O N 6
Additional Programming Notes