background image

26

 

A

Guidelines for Locating Smoke Detectors

Experience has shown that all hostile fires in family living units generate smoke to a greater or lesser
extent. Experiments using typical fires in family living units indicate that detectable quantities of smoke
precede detectable levels of heat in most cases. In existing homes, NFPA Standard 72 requires that a
smoke detector be installed outside each sleeping area and on each additional story of the family unit.

On smooth ceilings, detectors may be spaced 9.1m (30 feet) apart as a guide. Other spacing may be
required depending on ceiling height, air movement, the presence of joists, uninsulated ceilings, etc.
Consult National Fire Alarm Code NFPA 72, CAN/ULS-S553-M86 or other appropriate national
standards for installation recommendations.

Do not locate smoke detectors at the top of peaked or gabled ceilings; the dead air space in these
locations may prevent the unit from detecting smoke.

Avoid areas with turbulent air flow, such as near doors, fans or windows. Rapid air movement around
the detector may prevent smoke from entering the unit.

Do not locate detectors in areas of high humidity.

Do not locate detectors in areas where the temperature rises above 38

o

C (100

o

F) or falls below 5

o

C

(41

o

F).

Smoke detectors should always be installed in accordance with NFPA 72, the National Fire Alarm Code.
Smoke detectors should always be located in accordance with:

• Paragraph 2-2.1.1.1 of NFPA 72:

“Smoke detectors shall be installed outside of each separate sleeping

area in the immediate vicinity of the bedrooms and on each additional story of the family living unit,
including basements and excluding crawl spaces and unfinished attics. In new construction, a smoke
detector also shall be installed in each sleeping room.”

• Paragraph 2-2.1.1.2 of NFPA 72:

“Split level arrangement. Smoke detectors are required where shown.

Smoke detectors are optional where a door is not provided between living room and recreation room.”

The Smoke Detector is designed to use Eveready Energizer E91 Alkaline Batteries.
Do not use other brands of batteries with the Smoke Detector. Using brands other

than the Eveready Energizer will void UL approval, and may affect the system’s operation.

Summary of Contents for LCD55O1Z32-433

Page 1: ...433 NA version 4 1 WARNING Please refer to the System Installation Manual for information on limitations regarding product use and function and information on the limitations as to liability of the ma...

Page 2: ...2 Enroll Wireless Devices Using Zones 8 3 3 Enroll Program Wireless Keys 9 3 4 Identified Wireless Keys 10 3 5 Enrolling Programming Handheld Keypads 11 Section 4 Other Programming 12 4 1 Program Zone...

Page 3: ...er system If more keypads are required please select other DSC compatible keypads for the system being installed Specifications and Features Maximum Current Draw 260mA with back lighting boost on Freq...

Page 4: ...backplate to the wall in the desired location Use the screws provided 3 Before attaching the keypad to its backplate complete the keypad wiring as described in the next section 1 3 Wiring 1 Before be...

Page 5: ...section of the LCD5501Z32 433 Enter the following at each keypad installed on the system 1 Enter Installer Programming by pressing 8 Installer s Code 2 Press 000 for Keypad Programming 3 Press 0 for P...

Page 6: ...operly to the Keybus there is a problem with the Keybus wiring run the keypad does not have enough power 1 6 Downloading This product has an integrated PC5132 433 v4 1 receiver When downloading to thi...

Page 7: ...You can change the function of each key on every keypad Please see your system s Installation Manual for instructions on programming the keys and a complete list of all the function key options availa...

Page 8: ...press 1 2 or 3 1 ON Fire key enabled OFF Fire key disabled 2 ON Auxiliary key enabled OFF Auxiliary key disabled 3 ON Panic key enabled OFF Panic key disabled 5 When you are finished press to exit 2...

Page 9: ...r the door chime sound the Door Chime zone attribute must also be enabled in the control panel programming Please see your control panel Installation Manual To change the door chime sounds 1 Enter 8 I...

Page 10: ...v1 xpanel enter 5 digit serial numbers only When connecting the LCD5501Z32 433 to a PC5010 v2 x PC5015 v2 x PC5020 PC5008 PC1555 or PC580 panel follow the instructions below Old Wireless Device ESNs Y...

Page 11: ...have been enrolled 7 PC5010 PC5020 and PC5015 only PC5010 PC5020 and PC5015 only PC5010 PC5020 and PC5015 only PC5010 PC5020 and PC5015 only PC5010 PC5020 and PC5015 only By default all wireless keys...

Page 12: ...8 v2 0 and higher by turning section 015 option 4 off The Identified Wireless Key Opening option is only available with the PC1555 v2 1 PC580 v2 1 PC5008 v2 1 and higher PC5015 v2 2 and higher by turn...

Page 13: ...a wireless device Program the ESN as 000000 The wireless device for the zone will be removed NOTE You may need to remove power from the panel in order to clear troubles caused by deleted zones Now tha...

Page 14: ...the module is removed from the Keybus If you need to remove the LCD5501Z32 433 from an existing system you will have to disable supervision of the PC5132 4 3 Enable Supervision of Wireless Zones NOTE...

Page 15: ...gnal When the jamming signal is gone the RF Jam Detect zone closes and the system sends a tamper restore signal To enable RF jamming detection 1 Enter 8 Installer s Code 2 Enter programming section 80...

Page 16: ...Press The software for the receiver section will be restored to its factory default settings 4 Press to exit Installer Programming After a software default you must exit and then re enter Installer Pr...

Page 17: ...ackplate wait for 5 seconds then reattach the detector to its backplate Or hold a magnet near the raised line on the outer rim Then remove the magnet WLS907 WLS925L Open and close the contact by movin...

Page 18: ...433 higher will usually improve the reception If you move the LCD5501Z32 433 repeat the tests described in sections 5 1 and 5 2 on all the wireless devices Continue to test the devices until you have...

Page 19: ...y trouble The system will delay reporting the event to the central station for the number of days programmed for Zone Low Battery Transmission Delay in section 370 This will prevent unnecessary report...

Page 20: ...le placement test I get no result or Bad results Check the following see sections 5 1 and 5 2 for more information on testing devices Verify that you are testing the correct zone Verify that the corre...

Page 21: ...______I________I I________I________I 6 LCD5501Z32 433 Keypad Options Default Option On Off ON I________I 1 Local Clock Display Enabled Display Disabled ON I________I 2 Local Clock Displays AM PM Displ...

Page 22: ..._________________________________________I I________I I________I I________I I________I 16 I_____________________ _____________________________________________I I________I I________I I________I I______...

Page 23: ...1 Zone 11 l_____l_____l_____l_____l_____l_____l 12 Zone 12 l_____l_____l_____l_____l_____l_____l 13 Zone 13 l_____l_____l_____l_____l_____l_____l 14 Zone 14 l_____l_____l_____l_____l_____l_____l 15 Zo...

Page 24: ..._____l_____l_____l 53 Key 13 l_____l_____l_____l_____l_____l_____l 54 Key 14 l_____l_____l_____l_____l_____l_____l 55 Key 15 l_____l_____l_____l_____l_____l_____l 56 Key 16 l_____l_____l_____l_____l__...

Page 25: ...Disabled l________l Option 3 Zone 03 Supervision enabled Disabled l________l Option 4 Zone 04 Supervision enabled Disabled l________l Option 5 Zone 05 Supervision enabled Disabled l________l Option 6...

Page 26: ...Disabled l________l Option 7 Zone 23 Supervision enabled Disabled l________l Option 8 Zone 24 Supervision enabled Disabled 85 Zone Device Supervision Options 25 32 Zone Device Supervision Options 25 3...

Page 27: ...eys 9 16 Partition Assignments Wireless Keys 9 16 Partition Assignments Wireless Keys 9 16 Partition Assignments Wireless Keys 9 16 Partition Assignments Wireless Keys 9 16 Partition Assignments Defau...

Page 28: ...ns or windows Rapid air movement around the detector may prevent smoke from entering the unit Do not locate detectors in areas of high humidity Do not locate detectors in areas where the temperature r...

Page 29: ...y and all other warranties whether expressed or implied including all implied warranties of merchantability or fitness for a particular purpose And of all other obligations or liabili ties on the part...

Page 30: ...system may not properly alert occupants of a fire for a number of reasons some of which follow The smoke detectors may have been improperly installed or posi tioned Smoke may not be able to reach the...

Page 31: ......

Page 32: ...ust accept any interference including interference that may cause undesired operation of the device Ce dispositif satisfait aux exigences d Industrie Canada prescrites dans le document CNR 210 son uti...

Reviews: