1.3.1 System Verification
The complete fire alarm system must be verified for proper installation and operation when:
•
the initial installation is ready for inspection by the Local Authority Having Jurisdiction;
•
any system component is added, changed or deleted;
•
any programming changes are made;
•
system wiring has been altered or repaired;
•
system failure due to external influences such as lightning, water damage or extended
power outages has occurred.
1.3.2 Standby Power
The CFP-102/CFP-105 Fire Panel provides standby battery support for lead-acid rechargeable
batteries. The required capacity of the standby batteries must be calculated using the charts
and tables within the CFP-102/CFP-105
Installation Manual
for the period as required by
national or local codes and standards. Even though the calculation table within the CFP-102/
CFP-105
I
nstallation Manual
includes a safety margin, lead-acid batteries commonly used for
standby can have variable capacity as a result of age and ambient conditions. Periodic
inspection for damage and the batteries’ ability to support the attached equipment is highly
recommended.