P
R O G R A M M I N G
W
O R K S H E E T S
21
5.2 Panel Programming Worksheets
[001] Zone 1-16 Definitions
[011] First Panel Options Code
[012] Second Panel Options Code
[091] Clock Adjust
[091] System Time and Date
[902] FACP Event Buffer Viewing
[903] Module Supervisory Reset
[999] FACP Default
Zone Definitions
00
Null zone (not used)
03
Waterflow
01
Instant Fire
04
Supervisory
02
Verify Fire
05
4-Wire Verify Fire
Default
Default
01
Zone 1
01
Zone 4
01
Zone 2
01
Zone 5
01
Zone 3
Default
Option ON
Option OFF
OFF
Option 1
NAC1 is Temporal
NAC1 is Steady
OFF
Option 2
NAC2 is Temporal
NAC2 is Steady
OFF
Option 3
30 min. Automatic Signal Silence Enabled
Automatic Signal Silence Disabled
OFF
Option 4
NAC2 is Strobe
NAC2 is Standard Bell
OFF
Option 5
60 sec. Signal Silence Inhibit Enabled
Signal Silence Inhibit Disabled
ON
Option 6
Walk Test is Audible
Walk Test is Silent
OFF
Option 7
60 sec. Waterflow Zone Delay Enabled
Waterflow Zone Delay Disabled
ON
Option 8
Active Waterflow Zones can be Silenced
Active Waterflow Zones not Silenceable
Default
Option ON
Option OFF
ON
Option 1
Zone Trouble Auto Verifies Alarm
Zone Trouble Does not Auto Verify Alarm
OFF
Options 2-6
Future use
OFF
Option 7
Crystal Time Base Used
AC Time Base Used
OFF
Option 8
Daylight Savings Enabled
Daylight Savings Disabled
Default
060
(001-255 seconds)
Default
00:00
01
/ 01
/ 1999
HH:MM
MM / DD / YYYY
:
/
/