Clearance Requirements
5
Fireplace Insert Chimney,
Clearance Requirements and
Specifications
1. Insert must be installed in and existing masonry
or factory built fireplace. Maintaining all clearance to
combustibles.
2. Insert must be installed on a noncombustible
surface.
3. Locate and read clearance to combustibles in
manual before installing unit. The most important
consideration in installing your insert is adequate
clearance between the insert and any combustible
surface. An Insert that is located to close to a man-
tel, trim, furniture or any combustible materials may
cause a fire.
4. A noncombustible base must extent at least 16”
beyond front of insert and 8” beyond each side of
load and ash doors.
5. Do not connect this unit to a chimney flue serv-
icing other appliances. A “6” Class A” chimney liner
must extend from insert to top of chimney. It is rec-
ommended to wrap liner with foil faced insulation to
enhance performance of chimney.
Fireplace
Insert
S
id
e
w
a
ll
Mantle
Trim
Minimum Clearances to
Combustible Materials
Unit to Sidewall A - 10”
Unit to Right Side Facing B - 9”
Unit to Left Side Facing B - 9”
Unit to Top Facing C - 25”
Unit to Mantle D - 30”
Floor Protection in Front of Door E - 16”
Floor Protection each Side of Door F - 8”
Hot Air Regulator with Draft Intake
Chain Adjustment