English
I NS TAL LAT ION M ANUA L
5.9.3 Placing the concentric system
!Caution
-
Maintain a distance of at least 50 mm between the outside of the concentric system and the walls and/or
the ceiling. If the system is built in (for instance) a cove, it should be made with non combustible,
heat-resistant material all around it;
-
Use heat-resistant insulation material when passing through combustible material;
-
The rosette of the wall terminal is too small to seal the opening when passing through combustible
material. That is why you should first apply a sufficiently large heat-resistant intermediate sheet to the wall.
Then, the rosette is mounted on the intermediate sheet.
The roof terminal can end in a sloping and a flat roof.
The roof terminal can be supplied with an adhesive plate for a flat roof or with a universally adjustable tile for a
sloping roof.
!Caution
Some heat-resistant insulation materials contain volatile components that will spread an unpleasant smell for a
prolonged time; these are not suitable.
Place the concentric system as follows:
Ø
Build the system up from (the flue spigot of) the appliance.
Ø
Connect the concentric pipe pieces and, if necessary, the bend(s).
Ø
On each connection, apply a clip binding with silicon sealing ring.
Ø
Use a self-tapping screw to fix the clip binding to the pipe on locations that cannot be reached after installation.
Ø
Apply sufficient wall brackets, so that the weight of the pipes does not rest on the appliance.
Ø
Determine the remaining length for the wall or roof terminal and cut it to size, make sure the correct insertion
length is maintained.
Ø
Place the wall terminal with the (groove/folded) seam at the top;
Ø
Attach the wall terminal from the outside by means of four screws.
!Caution
When using the wall terminal, place the terminal with a downward slope of 1 cm / metre towards the outside, in
order to prevent rain water from raining in.
5.9.4 Connection to an existing chimney
It is possible to connect the appliance to an existing chimney.
A flexible SS pipe is placed in the chimney with a fitting diameter at the flue gas discharge pipe, for the discharge
of flue gases. The surrounding space is used to supply combustion air.
The following requirements apply when connecting to an existing chimney:
-
only allowed when used in combination with the special DRU chimney set. The installation regulation is
parat of the delivery;
-
the internal size should be at least 150 x 150 mm;
-
the vertical length has a maximum of 12 meters;
-
the total horizontal pipe length may have a maximum length that you can find in Appendix 2, Table 4;
-
the existing chimney should be clean;
-
the existing chimney should be tight.
For setting the appliance, the same conditions/instructions apply as for the concentric system described above.
UK
Summary of Contents for Excellence 60
Page 29: ...E n g l i s h INSTALLATION MANUAL UK 38C 1868 0 4...
Page 33: ...E n g l i s h INSTALLATION MANUAL UK 38P 0235 G A A F E D C B 19...
Page 34: ...E n g l i s h INSTALLATION MANUAL UK 38P 0233 38P 0234 A A 38P 0236 B C 20 21 22...
Page 35: ...E n g l i s h INSTALLATION MANUAL UK 38P 0237 F E G D B 2x 8x 38C 1750 A 24 23...
Page 37: ...E n g l i s h INSTALLATION MANUAL UK D A 38C 1756 F E D A F G 38C 1757 G 31 30...