18
6.1.2 Laser probe calibration thresholds 0295130, 24Vdc Out 4~20mA/2 NO (4 thresholds)
The laser probe has a display for viewing and programming mounted
on board. You can work in analogue (with signal from 4 to 20 mA) or
digital (two outputs and four intervention thresholds).
Attached is a table with the laser probe calibration parameters.
NOTE: To vary the laser probe calibration thresholds, contact DropsA personnel.
6.1.3 REED floating switch connection 0295150/0295160
LASER PROBE CALIBRATION
10 Kg reservoir
30 Kg reservoir
100Kg reservoir
Pos.
Level
Signal
Outlet
set-up
quot
a X
[mm
]
grease
quantity [Kg]
quota X
[mm]
grease quantity
[Kg]
quota X
(mm)
grease
quantity
(Kg)
A
Absolute
maximum
level
OUT 2= Fno
nsP2
220
11
220
23
220
90
C
Minimum
level
fsP2
300
5
490
5
850
17
B
Maximum
Level
OUT 1= Fno
nsP1
250
9
250
21
250
86
D
Absolute
minimum
level
fsP1
330
3
520
3
880
14