DriSteem CRUV Installation Instructions And Maintenance Operations Manual Download Page 11

11

CRU

®

V-DI TROUBLE-SHOOTING GUIDE 

(LW415 Electronic Water Level System Only)*

 PROBLEM

Humidifier will
not heat

Humidifier will
not fill

Water float
valve does not
close

Reduced or no
output even
though water is
at the proper
level

RECOMMENDED ACTION

Verify control voltage across secondary leads of
transformer.  Reset transformer circuit breaker.

Set humidistat to call. Inspect for faulty humidistat.

Check safety control. (Air flow switch, high limit
humidistat, etc.)

Verify control voltage from float switch and transformer
secondary common.

Check manual water supply. Valve, minimum 30 psi
water pressure.

Check to make sure that valve float & stem moves freely.

Check float valve seat.

Obstruction in drain valve will not allow complete
closure, clean or replace valve.

Close drain valve.

Float ball has water leak.  Float valve seat defective,
replace.

Readjust float valve rod, so water level reaches 1/4-3/8"
from overflow edge when water is at ambient or cold
state.  Excessive water pressure, 100 psi maximum.

Obstruction will not allow float valve to seat properly,
clean or replace with new seat.

Verify that proper voltage is being applied to heaters.
Check heaters (amp draw and compare to wire diagram
ratings).

Heater contactor not functioning, replace.  Service fuses
blown.  Auxiliary limit controls not allowing system to
operate (duct humidistat, air flow proving switch, etc.).
Reset, replace, or calibrate as required.  Faulty or
inaccurate humidistat, replace or calibrate.

On delay relay delay time is 10-15 seconds.  Check
relays.

Check for proper operation.

READY
WATER

Off

Off

On

On

POSSIBLE CAUSE

Control transformer

Humidistat is not calling

Safety controls open

Low water float switch

No water pressure at valve

Malfunctioning water float
valve

Plugged float valve

Open drain valve

Manual drain valve not closed

Malfunctioning float valve

Water passing into overflow
stand pipe

Float valve stuck

Heater malfunctioning

Malfunctioning control system

Time delay/interlock relays

Low water cut-off switch

*For VAPOR-LOGIC

2

 trouble-shooting, see the VAPOR-LOGIC

2

 Operations and Maintenance Manual.

Summary of Contents for CRUV

Page 1: ...AND SAVE THESE INSTRUCTIONS DRI STEEM CRUV ELECTRIC STEAM HUMIDIFIER Installation Instructions and Maintenance Operations Manual For Toll Free Customer Support Call 1 800 328 4447 cETL LISTED ETL LIS...

Page 2: ...ABLE OF CONTENTS TO THE PURCHASER AND THE INSTALLER Thank you for purchasing our CRU V humidification equipment We have designed and built this equipment to give you total satisfaction and many years...

Page 3: ...gure 3 1 The CRU V Humidifier CRUV 6 25 shown CRUV 2 4 30 and 34 not shown Cover Heater terminal cover Steam outlet Over flow SST ball valve Water supply Cover bolts Float switch Heater element OM 770...

Page 4: ...use a water seal and drain see examples in figures 4 2 and 5 1 The dispersion tube can also be placed vertically in the duct with some models see figure 5 2 Place the control cabinet or electrical sub...

Page 5: ...n Tube Lower Than Humidifier OM 774 1 Tee 3 5 127 mm Water Seal When horizontally mounting the dispersion tube in an air stream that is located lower than the CRUV humidifier a water seal to prevent s...

Page 6: ...1 40 9 600v 3 5 8 8 7 11 5 10 1 11 5 13 5 15 4 20 2 24 1 28 9 32 7 kW 2 0 4 0 6 0 8 0 10 0 12 0 14 16 0 21 0 25 0 30 0 34 0 CRU V Mechanical Electrical Specifications End Elevation OM 2002 Table7 2 C...

Page 7: ...he drain and fill valves remain open for ten more minutes flushing the chamber 4 The drain valve then closes the chamber refills and the fill valve closes The timer resets and the unit resumesnormalop...

Page 8: ...pair and push it on 2 Set the humidistat high enough so that unit will remain on call for at least one hour 3 After about 35 minutes of operation activation will take place causing the drain valve to...

Page 9: ...tight 8 Reconnect drain line union fill valve supply line electrical connections to drain thermal trip heaters fill valve and probe Connect steam hose to top of tank 9 Verify drain valve lever is in...

Page 10: ...ater conductivity 100 supply conductivity then consult factory micromhos cm 2 gr gal min Fill valve is stuck open Check valve for foreign matter Drain Valve not closed Check for correct water flow thr...

Page 11: ...nt or cold state Excessive water pressure 100 psi maximum Obstruction will not allow float valve to seat properly clean or replace with new seat Verify that proper voltage is being applied to heaters...

Page 12: ...l valve output Humidifier does not stop filling Lack of tank to probes electrical continuity water conductivity 100 micromhos cm 2 gr gal or 34 2 mg 1 min Add salt to the tank If this solves the probl...

Page 13: ...l l i f k c e h C p o t s t o n s e o d r e i f i d i m u H g n i l l i f e v l a v n i a r d n e p O r o n a e l C e r u s o l c e t e l p m o c w o l l a t o n l l i w e v l a v n i a r d n i n o i...

Page 14: ...e assy gasket 1 309750 003 8 probe assy CRUV 2 4 1 406270 8 probe assy CRUV 6 34 1 406275 9 3 4 electric valve 24v 1 505400 001 10 tank weldment 1 11 1 4 solenoid valve 24v w flying leads 1 505084 12...

Page 15: ...with conduit fitting 1 406050 100 7 probe assy gasket 1 309750 003 8 probe assy CRUV 6 34 1 406275 9 3 4 electric valve 24v 1 505400 001 10 tank weldment 1 11 1 4 solenoid valve 24 v w flying leads 1...

Page 16: ...float switch assy 1 9 probe assy gasket 1 309750 004 10 seal ring 1 4 18 npt 303 sst 1 306365 11 1 2 sst ball valve assy 1 505000 003 11 end of season drain valve assy not shown 1 505086 003 12 tank w...

Page 17: ...float switch assy 1 9 probe assy gasket 1 309750 004 10 seal ring 1 4 18 npt 303 sst 1 306365 11 1 2 sst ball valve assy 1 505000 003 11 end of season drain valve assy not shown 1 505086 003 12 tank w...

Page 18: ...n ordering Item Description Qty Part No 1 subpanel 13 X 15 1 165720 003 2 DIN rail 2 1 4 long 2 167765 0022 3 DIN rail 4 1 2 1 167765 0045 4 contactor 32A 1 407001 020 4 contactor 60A 1 407001 021 5 t...

Page 19: ...19 MAINTENANCE SERVICE RECORD DATE INSPECTED PERSONNEL OBSERVATION ACTIONS PERFORMED...

Page 20: ...DRI STEEM s limited warranty is made in lieu of and DRI STEEM disclaims all other warranties whether express or implied including but not limited to any IMPLIED WARRANTY OF MERCHANTABILITY ANY IMPLIE...

Reviews: