READ AND SAVE THESE INSTRUCTIONS

DRI-STEEM

CRUV

®

ELECTRIC STEAM HUMIDIFIER

Installation Instructions

and

Maintenance Operations Manual

For Toll-Free Customer Support,

Call:  1-800-328-4447

cETL LISTED

ETL LISTED

Summary of Contents for CRUV

Page 1: ...AND SAVE THESE INSTRUCTIONS DRI STEEM CRUV ELECTRIC STEAM HUMIDIFIER Installation Instructions and Maintenance Operations Manual For Toll Free Customer Support Call 1 800 328 4447 cETL LISTED ETL LIS...

Page 2: ...ABLE OF CONTENTS TO THE PURCHASER AND THE INSTALLER Thank you for purchasing our CRU V humidification equipment We have designed and built this equipment to give you total satisfaction and many years...

Page 3: ...gure 3 1 The CRU V Humidifier CRUV 6 25 shown CRUV 2 4 30 and 34 not shown Cover Heater terminal cover Steam outlet Over flow SST ball valve Water supply Cover bolts Float switch Heater element OM 770...

Page 4: ...use a water seal and drain see examples in figures 4 2 and 5 1 The dispersion tube can also be placed vertically in the duct with some models see figure 5 2 Place the control cabinet or electrical sub...

Page 5: ...n Tube Lower Than Humidifier OM 774 1 Tee 3 5 127 mm Water Seal When horizontally mounting the dispersion tube in an air stream that is located lower than the CRUV humidifier a water seal to prevent s...

Page 6: ...1 40 9 600v 3 5 8 8 7 11 5 10 1 11 5 13 5 15 4 20 2 24 1 28 9 32 7 kW 2 0 4 0 6 0 8 0 10 0 12 0 14 16 0 21 0 25 0 30 0 34 0 CRU V Mechanical Electrical Specifications End Elevation OM 2002 Table7 2 C...

Page 7: ...he drain and fill valves remain open for ten more minutes flushing the chamber 4 The drain valve then closes the chamber refills and the fill valve closes The timer resets and the unit resumesnormalop...

Page 8: ...pair and push it on 2 Set the humidistat high enough so that unit will remain on call for at least one hour 3 After about 35 minutes of operation activation will take place causing the drain valve to...

Page 9: ...tight 8 Reconnect drain line union fill valve supply line electrical connections to drain thermal trip heaters fill valve and probe Connect steam hose to top of tank 9 Verify drain valve lever is in...

Page 10: ...ater conductivity 100 supply conductivity then consult factory micromhos cm 2 gr gal min Fill valve is stuck open Check valve for foreign matter Drain Valve not closed Check for correct water flow thr...

Page 11: ...nt or cold state Excessive water pressure 100 psi maximum Obstruction will not allow float valve to seat properly clean or replace with new seat Verify that proper voltage is being applied to heaters...

Page 12: ...l valve output Humidifier does not stop filling Lack of tank to probes electrical continuity water conductivity 100 micromhos cm 2 gr gal or 34 2 mg 1 min Add salt to the tank If this solves the probl...

Page 13: ...l l i f k c e h C p o t s t o n s e o d r e i f i d i m u H g n i l l i f e v l a v n i a r d n e p O r o n a e l C e r u s o l c e t e l p m o c w o l l a t o n l l i w e v l a v n i a r d n i n o i...

Page 14: ...e assy gasket 1 309750 003 8 probe assy CRUV 2 4 1 406270 8 probe assy CRUV 6 34 1 406275 9 3 4 electric valve 24v 1 505400 001 10 tank weldment 1 11 1 4 solenoid valve 24v w flying leads 1 505084 12...

Page 15: ...with conduit fitting 1 406050 100 7 probe assy gasket 1 309750 003 8 probe assy CRUV 6 34 1 406275 9 3 4 electric valve 24v 1 505400 001 10 tank weldment 1 11 1 4 solenoid valve 24 v w flying leads 1...

Page 16: ...float switch assy 1 9 probe assy gasket 1 309750 004 10 seal ring 1 4 18 npt 303 sst 1 306365 11 1 2 sst ball valve assy 1 505000 003 11 end of season drain valve assy not shown 1 505086 003 12 tank w...

Page 17: ...float switch assy 1 9 probe assy gasket 1 309750 004 10 seal ring 1 4 18 npt 303 sst 1 306365 11 1 2 sst ball valve assy 1 505000 003 11 end of season drain valve assy not shown 1 505086 003 12 tank w...

Page 18: ...n ordering Item Description Qty Part No 1 subpanel 13 X 15 1 165720 003 2 DIN rail 2 1 4 long 2 167765 0022 3 DIN rail 4 1 2 1 167765 0045 4 contactor 32A 1 407001 020 4 contactor 60A 1 407001 021 5 t...

Page 19: ...19 MAINTENANCE SERVICE RECORD DATE INSPECTED PERSONNEL OBSERVATION ACTIONS PERFORMED...

Page 20: ...DRI STEEM s limited warranty is made in lieu of and DRI STEEM disclaims all other warranties whether express or implied including but not limited to any IMPLIED WARRANTY OF MERCHANTABILITY ANY IMPLIE...