36
CRUV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
MAINTENANCE
Tap/softened water
Humidifier De-scaling Solution
Scale buildup on humidifi er heaters acts as
an insulator, reducing humidifi er performance
while increasing energy costs. To keep
humidifi ers operating as effi ciently as possible,
remove scale with DriSteem's Humidifi er
De-scaling Solution, available for purchase
from your DriSteem representative or distributor.
The De-scaling Solution cleans without risk
of corroding humidifi er tanks or welds. The
De-scaling Solution also cleans surfaces
unreachable by hand scraping.
DriSteem's Humidifi er De-scaling Solution is the
only approved cleaner/de-scaler for use with
DriSteem humidifi ers. Use of other cleaners/
de-scalers may void your DriSteem warranty.
mc_021908_1410
• Clean and inspect probe rod assembly:
– Unplug the probe plug assembly, and leave ground wire connected
to tank.
– Unscrew probe rod assembly, and clean plastic probe housing,
ensuring that all passageways for water fl ow are clear.
– Clean probe rods using steel wool or similar mild abrasive material.
– Inspect composite plastic probe housing. If any signs of cracking,
roughness, or deterioration, replace assembly.
– When sliding probe housing into bracket from which it hangs, orient
housing so neither water fl ow slot directly faces tank wall at back
end of bracket.
• Secure the chamber cover, making sure the cover gasket is seated and
the chamber is sealed.
• Re-install evaporating chamber:
– Reconnect the fi ll line.
– Reconnect electrical plugs (the plugs are color coded).
– Reconnect the drain union.
– Reconnect the steam hose.
• Verify electrical connections:
– Verify that all DIN rail-mounted components are securely fastened to
DIN rail.
– Verify that all power terminal screws and lugs are tight from power
block to heaters.
– Verify that all plugs under the humidifi er cover are completely
plugged in.
• Move the drain valve lever back to the auto position.
• Turn on the water supply.
• Turn on the electrical power.
3.
Off-season maintenance
• Perform complete inspection and cleaning of the following:
– Heaters
– Probe
rods
– Skimmer port and water seal
– Humidifi er tank
• After cleaning, the humidifi er should remain empty until humidifi cation is
required.