CRUV INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
OPERATION
Start-up procedure
CAUTION
Damage from dry startup
In the event the humidifi er tank does
not contain water and the heaters
are energized, turn main power off.
Operation of the heaters without water
will cause damage to the humidifi er.
Before turning main power on, verify
that all wiring has been completed per
the wiring instructions in this manual
and the unit wiring diagrams.
mc_052410_1325
The CRUV humidifi er is available with either the LW series controller or the
optional Vapor-logic control system. If your system is equipped with the
Vapor-logic system, refer also to the
Vapor-logic Installation and Operation
Manual
as noted in the instructions below.
After the system is installed and connected properly:
1. Verify that the humidifier, controls, piping, electrical connections, steam
supply, and dispersion units(s) are installed according to the following:
• Installation instructions in this manual
•
Vapor-logic Installation and Operation Manual
(if using the Vapor-logic
control option):
– Installation
section
– Pre-installation
checklist
• Wiring diagrams shipped with humidifi er
• All governing codes
2. Confirm that proper grounding and an approved earth ground are
provided.
3. Verify that all electrical connections are secure before applying power.
4. Make sure all electrical covers are in place and secure. See Warning at
right.
5. Verify that the humidifier is mounted level and securely supported before
filling with water (see the operating weights in Table 4-1).
6. Verify that the humidifier is level front to back and side to side after it is full
of water.
7. Refer to “LW series controller” on Page 28 or the “Operation” section of
the
Vapor-logic Installation and Operation Manual
.
8. Perform all applicable “Start-up checklist” items on Page 28 or 29.
Note: During start-up, do not leave the humidifi er unattended.
9. Monitor humidifier operation through multiple fill cycles.
10. On tap/softened water units, water skims from the humidifier after every
fill cycle. Adjust the amount of skim by increasing or decreasing the skim
time. See "Skim duration" on Page 33.
At start-up, DriSteem recommends initially running the humidifi er with the
factory default setting for skim time.
Continue reading this section before proceeding to “Maintenance” beginning
on Page 34.
mc_060210_1400-CRUV
WARNING
Electric shock hazard
Only qualifi ed electrical personnel
should perform start-up procedure.
Contact with energized circuits can
cause property damage, severe
personal injury or death as a result of
electrical shock or fi re.
Make sure that all electrical covers
are in place and secure before turning
on electrical power. These include the
heater terminal cover, electrical panel
cover, and subpanel access panels.