Dri-Eaz CMC100 Owner'S Manual Download Page 2

07-01637F F391-A 2012-01  Warranty 07-01651 

Dri-Eaz Products, Inc. 

How to position the CMC100 dehumidifier 

Place your CMC100 dehumidifier in the middle of the space, 
away from walls, footings, ducts and other materials that may 
prevent the free flow of air around and through the unit.  

Keep unit level 

The unit must be level to operate properly. Four screw-in ad-
justable foot pads are provided. If the CMC is to be used on an 
uneven surface, these feet must be assembled and installed 
into the bottom of the CMC before placing the unit into service.  
1.  To assemble the feet, press the bolt through the center of 

the rubber foot and tighten the nut until it is snug against 
the rubber foot.  

2.  To install the feet into the CMC100 base, screw one foot 

assembly into the bottom of each corner of the unit. NO-
TICE: To avoid damage to the condensate drain outlet, do 
not tip the unit over onto the condensate drain side.  

3.  To level the unit with the feet, place a carpenter’s level on 

the top of the unit and adjust the footpads to raise or lower 
each corner of the unit until it is level.  

NOTICE: 

The CMC100 must be kept in an upright position. If it 

is necessary to place the unit on its side, such as during the 
installation of the feet, return the unit to the upright position and 

wait at least 10 minutes

 before starting the unit.  

Drain hose set-up 

During operation, water condenses out of the air and collects in 
a drain pan inside the unit. The CMC100 automatically pumps 
out this water through the drain hose outlet (see Figure 3). 
Dri-Eaz recommends directing the hose into a drain or well 
away from area to be kept dry.  
 

NOTICE:

 Do not place the end of the drain hose higher than 3 

feet (1 meter) above the top of the CMC, or leaking may occur. 

Pump operation 

Depending on operating conditions, the unit may produce con-
densate water intermittently, in a steady stream, or not at all for 
short periods of time. These functions indicate normal dehumi-
difier and pump-purge operations.  
NOTICE: To avoid spills, always secure the end of the drain 
hose so that the intermittent pumping action doesn’t shift the 
hose out of position.  
NOTICE: Do not allow the outlet of the drain hose to become 
submerged, blocked or otherwise subject to pressure that 
might reduce the ability of unit to pump water. 

Duct the outlet for optimum performance 

The processed air outlet is designed to accept standard 6 inch 
ducting (purchased separately). Properly installed, ducting can 
help circulate the air in the drying environment and improve 
drying efficiency. When using ducting, fasten it securely to the 
duct ring (see Figure 3). Place the open end of the duct some 
distance away from the unit. Use insulated flex ducting for the 
quietest operation. 

OPTIONAL CONFIGURATIONS 

The CMC100 features interchangeable panels that allow the 
unit to be adapted for use on shelves, small storage areas or in 
other locations where airflow might be obstructed. The damp 
air intake can be set up to draw in air from the end of the unit 
or from the side of the unit. Similarly, the output can be set up 
to exhaust dry air from the end of the unit or from the side of 
the unit. See Fig. 1.  

To change the airflow configuration, first unplug the CMC, then 
remove the four screws that hold each panel in place (see 
Figs. 2 and 3). Lift the panels out of the CMC frame. Replace 
the panels in the desired position and carefully tighten the 
screws. NOTE: When placing both intake and output panels on 
the side of the unit (option C, above right), Dri–Eaz recom-
mends attaching ducting to the output ring and placing the 
open end of the ducting some distance away from the CMC. 
This will help distribute the processed air more completely.  

Fig. 1: Airflow Options (Top View) 

 

 

 

 

 

 

 

 

 

 

Fig. 2: Parts Identification 

 

 

 

 

 

 

 

 

 

 

Recessed 
handles 

Control panel 

Filter door panel 
(remove 4 screws 
to access filter) 

Humid 
air inlet 

Interchangeable panels. 
See Optional Configura-
tions, left.  

Summary of Contents for CMC100

Page 1: ...ord to unplug The unit must be operated on a 115V 60 Hz circuit protected by a Ground Fault Interrupter GFI device This appliance is not intended for use by persons includ ing children with reduced physical sensory or mental ca pabilities or lack of experience and knowledge unless they have supervision or have been given instruction con cerning use of the appliance by a person responsible for thei...

Page 2: ... steady stream or not at all for short periods of time These functions indicate normal dehumi difier and pump purge operations NOTICE To avoid spills always secure the end of the drain hose so that the intermittent pumping action doesn t shift the hose out of position NOTICE Do not allow the outlet of the drain hose to become submerged blocked or otherwise subject to pressure that might reduce the...

Page 3: ...n you press the UP or DOWN buttons Af ter you have finished adjusting the setting the display will resume indicating the measured humidity and the CMC will automatically maintain humidity at the selected setting 2 In the STANDBY mode the display shows a double dash Unit does not operate in this mode Press the ON STANDBY button to return to ON mode Note The UP and DOWN buttons do not function in th...

Page 4: ...able filter Inspect the filter by removing the four filter door screws and sliding it out of the filter door panel see Figure 2 If the filter shows excessive buildup vacuum it clean and wash it in mild detergent Replace the filter in the filter door and close the door securely Note Do not operate the unit without the filter securely in place If the filter becomes torn or can no longer be adequatel...

Page 5: ...n 8 Inspect the drip tray Wipe clean with a cloth as necessary 9 Reattach the pump assembly to the pump bracket using the two bolts 10 Inspect the coil for dust accumulation Vacuum excess dust taking care not to damage any components Clean coils with Dri Eaz Coil Cleaner Be sure to wipe up any spills 11 Inspect the filter Clean in mild soap and water and dry tho roughly before reinstalling into th...

Page 6: ...ice Some values may be approximate PARTS INCLUDED WITH THE CMC Four leveling feet with mounting hardware 10 feet 3 meters of drain hose One hose clamp for attaching drain hose ADDITIONAL PRODUCT INFORMATION and current docu mentation is available at http cmc 100 dri eaz com FOR PARTS AND SERVICE CALL YOUR LOCAL DISTRIB UTOR or the Dri Eaz Service Department at 800 932 3030 www dri eaz com Visit wa...

Reviews: