- 17 -

 

 

 

Before  putting  the  safety  valve  into  operation  it  always  needs  to  be  checked  by  manual 
removal  of  the  membrane  from  the  valve  seat  and  turning  the  make-and-break  device 
button always in the direction of the arrow. After being turned, the button must click back 
into a notch. Proper function of the make-and-break device results in water draining through 
the safety valve outlet pipe. In common operation, such a check needs to be implemented at 
least once a month, and after each heater shutdown for more than 5 days. Water can drip 
from  the  safety  valve  through  the  drain  pipe;  the  pipe  must  be  freely  open  to  the 
atmosphere,  placed  vertically  and  shall  be  in  an  environment  free  of  temperatures  below 
freezing.  When  draining  the  heater,  use  a  recommended  drain  valve.  First,  close  water 
supply into the heater. 

 

Please find necessary pressure values in the table (Table 10). For proper safety valve operation, a backflow 
valve  must  be  mounted  on  the  input  pipes,  preventing  spontaneous  heater  draining  and  hot  water 
penetrating back into the water main. We recommend that the hot water distribution from the heater was 
as short as possible to minimise heat losses. At least one demountable joint must be mounted between the 
tank  and  every  supply  pipe.  Adequate  piping  and  fittings  with  sufficiently  dimensioned  maximum 
temperature and pressure values must be used.  

 

Heaters  must  be  provided  with  a  discharge  valve 
mounted  on  the  cold  service  water  inlet  to  the 
heater for potential disassembly or repair.  

When  assembling  the  security  equipment,  follow 
the standard. 

SAFETY VALVE 

STARTING 
PRESSURE 

[MPa] 

ADMISSIBLE 

OPERATING 

WATER 

HEATER 

PRESSURE 

[MPa] 

MAX 

PRESSURE IN 

THE COLD 

WATER PIPE 

[MPa] 

0,6 

0,6 

up to 0.48 

0,7 

0,7 

up to 0.56 

up to 0.8 

Table 10

 

 

2.4

 

FURTHER INFORMATION 

 

300-1000  litre  capacity  heaters  are  screwed  onto  the  bottom  wooden  palette  with  M12 
screws. When the heater is released from the palette and prior to its putting into operation, 
3 adjustable legs supplied as the product accessories have to be installed. With these legs, 
the heater may be positioned vertically to the base, within 10 mm. 

 

 

 

 

Summary of Contents for OKCE 100 S/2.2 kW

Page 1: ...Pa OKCE 125 S 2 2 kW OKCE 250 S 2 2 kW OKCE 400 S 1 MPa OKCE 160 S 2 2 kW OKCE 250 S 3 6 kW OKCE 500 S 1 MPa OKCE 160 S 3 6 kW OKCE 750 S 1 MPa OKCE 200 S 2 2 kW OKCE 1000 S 1 MPa Dru stevn z vody Dra...

Page 2: ...00 S 3 6 kW OKCE 250 S 2 2 kW OKCE 250 S 3 6 kW OKCE 300 S 1 MPa OKCE 400 S 1 MPa OKCE 500 S 1 MPa 11 2 2 4 WIRING FOR OKCE 300 S 1MPa OKCE 400 S 1 MPa OKCE 500 S 1MPa OKCE 750 S 1MPa OKCE 1000 S 1MPa...

Page 3: ...d would like to thank you for your decision to use a product of our brand With this guide we will introduce you to the use construction maintenance and other information on electrical water heaters Th...

Page 4: ...them The tank is insulated with 65 mm of polyurethane foam The heater shield consists of a steel powder paint coated sheet the connecting parts are metal coated For heaters 100 125 l is a flange weld...

Page 5: ...KCE 100 S 2 2 kW OKCE 125 S 2 2 kW A 885 1050 B 885 1050 C 126 126 D 524 54 L 520 620 1 3 CONSTRUCTION AND GENERAL HEATER DIMENSIONS OKCE 100 S 2 2 kW OKCE 125 S 2 2 kW Figure 1 3 4 vn j 3 4 vnit n 1...

Page 6: ...4 vn j 3 4 vnit n 3 4 vn j 3 4 vnit n TYPE OKCE 160 S 2 2 kW OKCE 200 S 2 2 kW OKCE 250 S 2 2 kW A 1047 1357 1537 B 966 1279 1459 C 519 859 1059 D 168 168 168 E 79 79 79 F 242 242 242 TYPE OKCE 160 S...

Page 7: ...S 1MPa A 304 292 B 79 65 C 514 385 D 650 700 E 1194 1269 F 1289 1414 G 1790 1790 H 1920 1924 I 245 273 OKCE 300 S 1 MPa Figure 4 OKCE 400 S 1 MPa OKCE 500 S 1 MPa Figure 5 A 1578 B 724 C 79 D 650 F 75...

Page 8: ...W OKCE 160 S 2 2 kW OKCE 200 S 2 2 kW OKCE 250 S 2 2 kW OKCE 160 S 3 6 kW OKCE 200 S 3 6 kW OKCE 250 S 3 6 kW CAPACITY l 100 125 160 220 259 WEIGHT kg 42 49 58 72 80 67 81 89 OPERATING PRESSURE OF ACC...

Page 9: ...ulations and standards also conditions for connection defined in local electric and water works have to be adhered to as well as the installation and operation manual The temperature at the place of h...

Page 10: ...ts of the heater is IP 45 Power input of electric element is 2000 W Figure 7 2 2 2 WIRING FOR OKCE 100 S 2 2 KW OKCE 125 S 2 2 KW Wiring scheme is attached to the heater wiring on the cover Connect re...

Page 11: ...serted all the way in first the thermostat and then the safety fuse The performance of heating unit may be adjusted based on either required heating time or connecting possibilities of electric energy...

Page 12: ...ostat to the snowflake sign preventing the water from freezing or turn off the inlet of electricity to the heater Connection repairs and wiring inspections may only be implemented by company person au...

Page 13: ...kW OKCE 300 S 1 MPa OKCE 400 S 1 MPa OKCE 500 S 1 MPa TPK 210 12 5 9 kW TPK 210 12 8 12 kW Mounting 12 x M12 Figure 12 Wiring scheme Notice Factory connection must not be changed Cover of wiring with...

Page 14: ...rconnect the clips on the 1 10 terminal board in accordance with the following schemes 3 kW 1 PE N AC 230 V 50 Hz 3 kW 2 PE N AC 400 V 50 Hz 4 kW 3 PE N AC 400 V 50 Hz 6 kW 3 PE N AC 400 V 50 Hz OKCE...

Page 15: ...SE 377 11 SE 378 14 SE 377 16 SE 378 19 Capacity Flanges size Time of heating from 10 C to 60 C hours l Mm 8 6 5 4 3 2 5 2 1 5 300 flange 210 RDU 18 2 5 RDU 18 3 RDU 18 3 8 RDU 18 5 RDU 18 6 RDW 18 7...

Page 16: ...ominal clearance of safety valves is defined by standard 300 l heaters are not equipped with a safety valve The safety valve must be easily accessible as close to the heater as possible The input pipe...

Page 17: ...t pipes preventing spontaneous heater draining and hot water penetrating back into the water main We recommend that the hot water distribution from the heater was as short as possible to minimise heat...

Page 18: ...he operating and then the safety thermostat b Open the hot water valve on the combination faucet c Open the cold water inlet valve to the heater d When the water starts flowing through the hot water v...

Page 19: ...the company in charge of service affairs clean and exchange the anode When discharging water from the heater the mixing valve of the hot water tap must be open in order to avoid creating underpressur...

Page 20: ...adjusted against the fixed point on the control panel Figure 19 Figure 19 Adjusting the thermostat selector to the left backstop does not mean permanent shut off of the heating element When the heater...

Page 21: ...try to repair the failure yourselves Seek either expert or service help It does not take much for an expert to remove the defect When making a repair appointment report the type and serial number you...

Page 22: ...use 4 2 DISPOSAL OF PACKAGING MATERIAL AND FUNCTIONLESS PRODUCT A service fee for providing return and recovery of packaging in which the water heater was delivered The service fee was paid pursuant...

Page 23: ...o put the two zip insulation sides together Figure 19 so that the insulation does not draw down and the openings in the insulation fit the boiler inputs and outputs It must be secured that before clos...

Reviews: