Dragon Wholesaling 564 Diamond-Fyre Installation Manual Download Page 17

 

Installation

  

(for qualified installers only)

 

17 

© Travis Industries 

4101014 

100-01257_000 

Gas Line Requirements 

 

The gas line must be installed in accordance with all local codes, if any; if not, follow ANSI 223.1 and 
the requirements listed below. 

 

The fireplace and gas control valve must be disconnected from the gas supply piping during any 
pressure testing of that system at test pressures in excess of 1/2 psig.  For pressures under 1/2 psig, 
isolate the gas supply piping by closing the manual shutoff valve. 

 

Leak test all gas line joints and the gas control valve prior to and after starting the fireplace. 

Fuel 

 

This fireplace is designed either for natural gas or for propane (but not for both).  Check the sticker on the top of 
the gas control valve to make sure the correct fuel is used. 

Gas Line Connection 

 

Installation must be performed by a qualified installer, service agency or the gas supplier (In Massachusetts a 
licensed plumber/gasfitter). 

Gas Inlet Pressure 

 

Standard Input Pressure 

 

Natural Gas 

7" W.C. (1.74 kPA) 

 

Propane 

13" W.C. (2.73 kPA) 

 

If the pressure is not sufficient, make sure the piping used is large enough, the supply regulator is adequately 
adjusted, and the total gas load for the residence does not exceed the amount supplied.   

 

The supply regulator (the regulator that attaches directly to the residence inlet or to the propane tank) should 
supply gas at the suggested input pressure listed above.  Contact the local gas supplier if the regulator is at an 
improper pressure. 

Summary of Contents for 564 Diamond-Fyre

Page 1: ...call gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualifie...

Page 2: ...nstallation requirements for the 564 DF fireplace For operating and maintenance instructions refer to the 564 DF Owner s Manual part 100 01258 Listing Details This appliance was listed by SAI Global t...

Page 3: ...nt Requirements 21 Vent Clearances 21 Altitude Considerations 21 Approved Vent 22 Vent Installation 22 Approved Vent Configurations 23 Restrictor Position 23 Exhaust Restrictor Adjustment 23 Intake Re...

Page 4: ...gas NG or propane LP Burning the incorrect fuel will void the warranty and safety listing and may cause an extreme safety hazard Direct questions about the type of fuel used to your dealer Check the l...

Page 5: ...except the included components Do not throw this manual away This manual has important operating and maintenance instructions that you will need at a later time Always follow the instructions in this...

Page 6: ...Input Per Hour 20 500 20 500 Maximum Megajoules MJ Input Per Hour 21 6 21 6 Heating capacity will vary with floor plan insulation and outside temperature Efficiency rating is a product thermal effici...

Page 7: ...back and sides of the fireplace See the section Vent Requirements See the section Minimum Framing Dimensions Drywall Top Vent Configuration Rear Vent Configuration See the section Gas Line Installati...

Page 8: ...secure the standoff Bend the standoff in the numbered sequence shown above Remove the screw below the standoff b 1 2 3 c The standoffs are shipped in the flat position Make sure to follow the instruc...

Page 9: ...e diffuser when changing the vent configuration Converting the Fireplace to Top Vent Configuration Remove the 4 screws securing the outer flue assembly Place the screws and assembly aside NOTE Use a m...

Page 10: ...he rear facing exhaust port with the same screws Verify the gasket on the intake cover plate is in place then attach it to the rear of the fireplace using the screws removed earlier Verify the gasket...

Page 11: ...r non combustible surface not on linoleum or carpet This heater may be placed in a bedroom Please be aware of the large amount of heat this appliance produces when determining a location Clearances Wh...

Page 12: ...1 25mm to the sides 1 25mm below and 4 102mm above the vent to combustibles Included Firestop required Part 250 00747 Center of Rear Vent HINT place the fireplace so the center line is at least 5 127m...

Page 13: ...e to a position to the left rear of the fireplace 36 1 2 927mm 33 1 2 851mm 16 1 2 419mm WARNING A cut out for the gas line may be required on the framing See the dimensions under Gas Line Connection...

Page 14: ...r tab out 90 use a screwdriver if necessary Fireplace Drywall Framing Nailing Bracket TOP VIEW 1 2 13mm Drywall 5 8 0 625mm Drywall There are four nailing brackets on the front of the fireplace Follow...

Page 15: ...lation uses the framing dimensions shown in the illustration below NOTE all clearances still apply 7 178mm Approximate varies due to vent installation 44 1 2 Min 1130mm Minimum 1 2 13mm Clearance NOTE...

Page 16: ...Industries 4101014 100 01257_000 Corner Installations Top Vent Configuration A typical 45 installation uses the framing dimensions shown in the illustration below NOTE all clearances still apply 14 1...

Page 17: ...ther for natural gas or for propane but not for both Check the sticker on the top of the gas control valve to make sure the correct fuel is used Gas Line Connection Installation must be performed by a...

Page 18: ...er plate has a 7 8 0875mm diameter hole covered with a push plug in line with the gas inlet on the gas control valve By rotating the plate 180 the hole may be re located You may also secure the plate...

Page 19: ...hut off prior to working on any electrical lines The appliance when installed must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical...

Page 20: ...ow If you wish to bypass the switch connect the thermostat on off switch wires directly to the green and white wires see c below If you wish keep the switch series re align the wires as shown in item...

Page 21: ...s use the high wind termination if available from the vent manufacturer Vent Clearances The vent must maintain the required clearance to combustible materials to prevent a fire Do not fill air spaces...

Page 22: ...for details Always use the high wind cap or high wind sconce cap part 58DVA HSCH or 46DVA HSCH Installation instructions for Simpson Dura Vent may be found at www duravent com 6 5 8 168mm Diameter Ve...

Page 23: ...ptable vent configurations detail the correct vent restrictor positions Exhaust Restrictor Adjustment If the diffuser is required to be in position 2 you may wish to adjust the diffuser while the exha...

Page 24: ...Travis Industries 4101014 100 01257_000 Intake Restrictor Adjustment Loosen the two screws holding the intake restrictor in place 1 4 Socket Slide the restrictor down to the lower position and tighten...

Page 25: ...on 2 is flattened See the directions below to change the diffuser to position 2 Back Wall of Firebox Firebox Roof Remove the exhaust restrictor 1 4 Nutdriver Remove the diffuser 1 4 Nutdriver Secure t...

Page 26: ...5 Elbow Termination See the charts below to determine maximum vent 3 feet 915mm 0 feet mm 0 feet mm 4 max 610mm Exhaust Restrictor 0 stock Intake Restrictor 1 stock Diffuser Position 1 stock Vent with...

Page 27: ...et 1 5 m 10 feet 3 m 5 feet 1 5 m 10 feet 3 m 0 feet 15 feet 4 5 m 20 max 6 m 10 feet 3 m 15 feet 4 5 m 15 feet 4 5 m 20 max 6 m 10 feet 3 m 15 feet 4 5 m 22 max 6 7 m 22 max 6 7 m Exhaust Restrictor...

Page 28: ...t 3m 0 feet 15 feet 4 5m 20 max 6m 10 feet 3m 15 feet 4 5m 15 feet 4 5m 20 max 6m 10 feet 3m 15 feet 4 5m 40 max 12m Exhaust Restrictor 6 Intake Restrictor 2 Diffuser Position 2 25 feet 7 5m 30 feet 9...

Page 29: ...et 20 feet 6m 20 feet 6m 5 feet 1 5m 10 feet 3m 5 feet 1 5m 10 feet 3m 0 feet 15 feet 4 5m 20 max 6m 10 feet 3m 15 feet 4 5m 15 feet 4 5m 20 max 6m 10 feet 3m 15 feet 4 5m 21 max 6 4m 21 max 6 4m Exha...

Page 30: ...m 10 feet 3m 5 feet 1 5m 10 feet 3m 0 feet 15 feet 4 5m 20 max 6m 10 feet 3m 15 feet 4 5m 15 feet 4 5m 20 max 6m 10 feet 3m 15 feet 4 5m 40 max 12m Exhaust Restrictor 6 Intake Restrictor 2 Diffuser Po...

Page 31: ...with local installation codes and the requirements of the gas supplier G Minimum 48 1219mm clearance from any adjacent building H Minimum 84 2134mm clearance above any grade when adjacent to public wa...

Page 32: ...ring the fireplace must be raised so the base of the unit is above the carpet surface or flooring material Floor Mounted Fireplaces Raised Fireplaces A hearth is not required when the fireplace is rai...

Page 33: ...ce Tile or other non combustible facing may be placed on the front of the fireplace see Facing Overview on page 34 for further details Drywall Installation Drywall Installation Drywall may be installe...

Page 34: ...up to this location 1 25mm above the base of the fireplace The fireplace may be raised to accommodate thicker hearth materials Masonry Line Hearth Line Tile Line Tile Line Masonry Line Tile Line Mason...

Page 35: ...air Raised Fireplaces Facing is installed 1 maximum 25mm above the base of the fireplace Facing is installed to this edge of the fireplace FRONT VIEW Tile Line Tile Line Hearth Line Tile Line 27 3 4...

Page 36: ...ce Note how the facing extends 1 25mm above the base of the fireplace 1 25mm Fireplace Support Floor Drywall Tile or other facing under 1 25mm thick Face Floor Max 1 25mm Hearth note how it extends un...

Page 37: ...Drywall Fireplace Drywall Framing Nailing Bracket Masonry TOP VIEW Protruding Masonry Fireplace Drywall or cement board etc Framing NOTE The nailing brackets are not used for this type of installatio...

Page 38: ...500674 The template helps locate and support the masonry as it being installed Masonry Line Hearth Line Drywall Floor Mounted Fireplaces or Raised Hearths Build the hearth 1 max 25mm above the base of...

Page 39: ...The masonry extends 1 25mm above the base of the fireplace 1 25mm Fireplace Support Floor Floor Mounted Fireplace with Hearth SIDE OF FIREPLACE Drywall Masonry or other non combustible over 1 25mm thi...

Page 40: ...3 4 0 75mm or less they may be placed directly to the side but not in front of the fireplace Non combustible mantel columns do not have a minimum clearance 38 1 2 978mm 12 305mm Maximum Non Combustibl...

Page 41: ...2mm EXTERIOR WALLS When installed with a 2x4 51mm X 102mm exterior wall the termination may not fit flush against the exterior wall You may wish to place framing around the termination to fill the gap...

Page 42: ...Section Firestop NOTE FOR 2 x 4 51mm X 102mm EXTERIOR WALLS When installed with a 2x4 51mm X 102mm exterior wall the termination may not fit flush against the exterior wall You may wish to place frami...

Page 43: ...per towel 4 Install the four AA batteries included in the owner s pack into battery holder see the illustration below The AA batteries act as a power backup in case the household AC power goes out Ins...

Page 44: ...orward More Air Backward Less Air Adjusting the Air Shutter Air Shutter Adjustment 10 Turn the flame adjust knob to its highest position the flames should not contact the top of the firebox Check the...

Page 45: ...s Open the four latches holding the glass frame in place start with the bottom follow the directions shown to the right a Lift the glass frame up and pull it forward to remove b Re Attaching the Glass...

Page 46: ...ed 1 4 turn when it is disengaged Follow the directions below to re install the latch if it becomes loose Top of Firebox Hold the latch at an angle and insert it into the slot on the glass frame ancho...

Page 47: ...istent Any cleaning may lead to unequal coloring If soot forms on the fireback we recommend brushing it off with a soft cloth or brush CLEANING ENAMEL FIREBACKS We recommend cleaning the enamel surfac...

Page 48: ...ide 5 Remove the two side fireback clips from the firebox ceiling They are located at the outward edges of the firebox near the glass opening The side fireback clip has a keyhole slot It can be remove...

Page 49: ...restrictor position consult the installation manual for details 9 Before replacing the glass tray use a screwdriver to bend the four light deflectors up as shown below The deflectors must be bent up...

Page 50: ...to prevent light from exiting the sides of the front glass tray skirt Place the shield as shown in the photos below for both sides 14 Slide the front glass tray skirt over the front edge of the glass...

Page 51: ...7_000 Crushed Glass Installation Crushed Glass Install the crushed glass on the glass tray as shown below Use 10 pounds of crushed glass 4 5 Kg The glass should cover the glass tray and be evenly disp...

Page 52: ...on Instructions Install the conversion kit prior to installing the gas line to ensure proper gas use 1 Remove the glass see page 43 Remove the crushed glass if installed page 47 2 Remove the cast burn...

Page 53: ...Industries 4101014 100 01257_000 4 Remove the side burners Each side burner has a bracket that inserts over a tab on the firebox floor Lift the burner up and slide it away from center to remove 5 Remo...

Page 54: ...LP orifices prior to installation Use the chart below to identify the correct orifices Center Sides NG 53 60 LP 63 70 Screw each LP orifice in so the orifice protrudes 15 16 24mm indicating full inse...

Page 55: ...ard the screws see a below holding the stock regulator in place see b below Remove the stock regulator and gasket see c below Place the LP regulator in place making sure the pre fitted gasket see c be...

Page 56: ...need to press on the grill to get the tab over the bushing this prevents the grill from accidentally falling off Bend the tab outward on both sides This is the end stop for the lower grill it allows...

Page 57: ...0 Special Instructions Regarding Australian Fireplaces with Shadowbox Face The Australian fireplaces use a 240v rheostat This rheostat operates in reverse to the 120v version If you are using the Shad...

Page 58: ...le Build InwithHorizontalTermination 42 Installation Options 6 Installation Overview 7 Intake Restrictor Adjustment 24 Listing Details 2 LP Conversion Instructions 52 Mantel Requirements 40 MinimumFra...

Reviews: