Dräger VarioGard
39
Installation
7
Installation
Details on the mechanical installation and the wiring diagram are
available in the following documents:
VarioGard central unit
Installation according to the installation instructions 90 33 231.
VarioGard 3x00 transmitter
Installation according to the installation instructions 90 33 163.
VarioGard battery module
Installation according to the installation instructions 90 23 579.
VarioGard Relay Module
Installation according to the installation instructions 90 23 577.
VarioGard Converter Module
Installation according to the installation instructions 90 23 578.
VarioGard Repeater Module
Installation according to the installation instructions 90 23 729.
7.1
Electrical installation
Error message or
warning
Cause
Remedy
Transmitter 1
Error !
Electronic fault
Replace transmitter
or have it repaired by
Dräger Service.
Transmitter 1
Mainten. recommend
!
Transmitter operating
time about to expire.
Install new transmitter or
have Dräger Service
check the transmitter.
Transmitter 1
Mainten. necessary !
Transmitter operating
time has expired and the
sensor is no longer
working properly.
Install new transmitter or
have Dräger Service
check the transmitter.
Dräger VarioGard
Emerg. power supply
!
Central unit not
connected to mains.
Check installation and
correct.
Voltage loss
Correct voltage loss.
WARNING
The VarioGard system wiring may only be routed and
connected by an electrician in accordance with the relevant
regulations.
Do not connect the instruments to the power supply before
the wiring has been completed and tested.
NOTICE
Shielded cables are not required.
!
i
i
Summary of Contents for VarioGard
Page 2: ......
Page 179: ...Dr ger VarioGard 179 1 Dr ger Dr ger 195 2 i i...
Page 185: ...Dr ger VarioGard 185 A1 A2 A3 A4 4 2 5 6 4 Escape Enter 5 1 i i ESC ESC...
Page 187: ...Dr ger VarioGard 187 6 1 1 2 3 4 5 i i...
Page 198: ...198 Dr ger VarioGard 9 3 9 4 VarioGard 3x00 2 VarioGard 3x00 2...
Page 278: ......
Page 279: ......