34
Dräger VarioGard
Configuration
If the concentration at one or more transmitters exceeds an
alarm threshold:
Alarms A1, A2 and A3 are not
latching and cannot be
acknowledged!
The LED (1) on the central unit
and on the transmitter concerned
flashes according to the particular
alarm; see table "Alarm states".
Alarm states (factory default setting)
The alarm relays are switched according to the particular alarm,
see table "Alarm states".
VarioGard
ESC
00633185.eps
1
Display on the central unit e. g.:
If several transmitters are in alarm state at
the same time, all the transmitters in alarm
state will be shown on the display one
after the other.
Transmitter 4
68 ppm NH3
I A1
NOTICE
Relays are designed as outputs. The normal state corresponds
with the selected wiring in the state "No alarm".
i
i
Alarm
LED
Acoustic
alarm
Relay 1
Relay 2
Relay 3
Relay 4
Relay 5
No power
red
no
closed
closed
closed
closed
closed
none
green
no
open
open
open
open
open
A1
red
no
closed
open
open
open
open
A2
red
no
closed
closed
open
open
open
A3
red
no
closed
closed
flashing
open
open
A4
red
yes
closed
closed
flashing
closed
open
Summary of Contents for VarioGard
Page 2: ......
Page 179: ...Dr ger VarioGard 179 1 Dr ger Dr ger 195 2 i i...
Page 185: ...Dr ger VarioGard 185 A1 A2 A3 A4 4 2 5 6 4 Escape Enter 5 1 i i ESC ESC...
Page 187: ...Dr ger VarioGard 187 6 1 1 2 3 4 5 i i...
Page 198: ...198 Dr ger VarioGard 9 3 9 4 VarioGard 3x00 2 VarioGard 3x00 2...
Page 278: ......
Page 279: ......