20
Configure Serial Port via TTY
9.1
Serial port configuration
1. To enter configuration setting for the Serial Port, login to the TTY interface and press
C)onfig
>
s(E)rial
.
2. Press the hot keys to toggle through the following options. (* Indicates default settings:)
NOTE
: Default settings may not reflect the primary interface that shipped in the unit.
·
Port Type
: 232*, 485
·
Baud
: 9600*, 57600, 19200, 9600, 4800, 2400, 1200
·
Parity
: None*, even, odd
·
Stop bits
: 1*, 2
3. Set the RTS head / tail (Carrier time) Suggested settings are: 0,0 if using RS232.
Quick Turn Up
10
The next sections of this manual will walk you through some of the most common tasks for using the TempDefender
G2. You will learn how to send email notifications, and send SNMP traps to your alarm master - all using the Web
browser. For details on entering your settings into each Web browser menu, the section "Provisioning Menu Field
Descriptions" section.