3
Specifications
2
NetGuardian AAR HC
Hardware
Dim ens ions :
17.026” W x 1.19” H x 7.25” D
Dis cr ete Alar m Inputs :
20 (reversible) HC Only,
5
12 TTL Dry,
8 TTL 5v Biased
Mounting:
19” or 23” Rack
2
Dis cr ete Alar m Length:
2000Ft. per Alarm
Weight:
3.5lb (1.56 kg)
Analogs :
20 (HC)
Pow er Input:
+48VDC (36 to 72 VDC)
Input Range:
-92 to +92 VDC or 4 to 20mA
4
Analog Accur acy:
± 1% of Analog Range
3
Cur r ent Dr aw :
100mA max @ 48 VDC
Contr ol Outputs :
48 Relays (HC Only) 16 Form C, 24
Form A ground closure, 8 Form A
12v closure
200mA max @ 24 VDC
Max Voltage: 60 VDC/120 VAC
Fus e:
3/4 Amp GMT
Max Current: 1A AC/DC
Audible Inter faces :
Alarm Speaker
Oper ating Tem p:
32° to 140°F (0° to 60°C)
Vis ual Inter faces :
8 Front Panel LEDs
Indus tr ial Oper ating Tem p:
-22° to 158°F (-30° to 70°C)
4 Back Panel LEDs
Oper ating Hum idity:
0% to 95% non-condensing
1
Har dw ar e Inter faces :
4 : DB50 (Discrete Inputs / Control
Relays/Analogs) HC Only
1 RJ45 10/100BaseT Ethernet
Stor age Tem p:
-22° to 257°F (-30° to 125°C)
1 RS-232 Serial (or optional RS-485)
Stor age Hum idity:
0% to 95% non-condensing
1 USB Craft Port
1 RJ-11 D-Wire sensor network
(optional)
MTBF:
60 Years
RoHS:
RoHS 5 Approved
Or der ing Options :
D-Wire, 4-Port 10/100 Switch
Software
Dow nloadable Fir m w ar e:
Yes
SNMP Suppor t:
v1, v2c, v3
Built-in Web Inter face:
Yes
D-Wir e Sens or Suppor t:
Temp, Temp/Humidity
Br ow s er Suppor t:
IE9, IE10, Firefox
Ping Alar m s :
32
Pr otocols :
.
DCPx, TELNET, HTTP, Email, HTTPS
(up to SSL v3)
OS Suppor t:
Windows 95, 98, NT, ME, XP, 2000,
Vista, 7
32/64bit
Note:
1
Valid if hardware option is included.
2
Minimum lengths determined with TTL voltage level alarms. Actual distance may vary.
3
Current measured at rated voltage with all controls latched and all alarms triggered.
4
See analog section in manual for detailed analog accuracy breakdown.
5
12v max input
* This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will
be required to correct the interference at his own expense.
Summary of Contents for D-PK-NGAAR
Page 16: ...12 HC Pinouts 6 1 NetGuardian AAR HC Back Panel Top Board Connectors Bottom Board Connectors ...
Page 17: ...13 MC Pinouts 6 2 NetGuardian AAR MC Back Panel Top Board Connectors Bottom Board Connectors ...
Page 18: ...14 ...
Page 19: ...15 LC Pinouts 6 3 NetGuardian AAR LC Back Panel Alarm Analog Relay Connections ...
Page 68: ...64 Value 99 1 49 64 ...
Page 77: ...73 ...