Introduction: 

The residual current device type B  DER3BDUAL series, fully compliant with IEC 60947-2: 2019, can be used in LV network in DC (pole to ground), AC (TT, 

TN)  or  mixed  current.  The  series  is  recommended  for  the  use  with  inverter,  UPS,  frequency  converters,  photovoltaic  system,  production  facilities  on  construction 
sites, lifts, lathes, milling machines, since these devices, that generate direct or mixed residual current, which the normal residual current devices type A-AC don't 
detect, are becoming more common.  

INSTALLATION SUGGESTIONS AND SAFETY PRECAUTION: 

All installation and maintenance operations must be carried out by qualified personnel in the absence of voltage and in a total electrical safety regime, in compliance 
with the safety regulations.  
1) Before powering the DER3BDUAL, check that all connections have been executed properly. 
2) ALWAYS install DER3BDUAL by using Dossena toroidal transducers B and D series (DER B  D toroid). 
3) The cross-section of the conductors must be such that the total resistance of each DER3BDUAL ↔transducer connections does not exceed 0.5Ω. 
4) Minimize the distance connections between DER3BDUAL and transducers and keep them away from power cables; use twisted shielded cables, with the shield 
connected to ground at one point only (keep the measurement circuit separate from test circuit). 
5) 

At the first commissioning perform the calibration of toroids, please view section SETUP item CAL.

 

NORMAL VIGILANCE (GREEN DISPLAY)

 

Pag 1: 

The system alternating residual current (

I∆

 in Ampere AC TRMS) and direct residual 

current (

I∆ 

in Ampere DC TRMS) are shown in this page.

       

Pag 2: 

 The system total residual current (

I∆

 in Ampere) and relative % value of residual 

current in AC (alternating current) and DC (direct current) are shown in this page.

 

Others parameters in either pages: 
I∆n= 

Threshold of the nominal residual current. 

∆t= 

Limiting non-actuating time.

 

histogram

 = Instantaneous histogram that identifies residual current in DC (solid segment) 

and AC (diagonal stripes segment) .

 

AL

= Alarm threshold. 

Keys  function (for 6Din version the keys are on the right side): 

: Push this button to display Pag1 (value in TRMS) or Pag 2 (% value). 

: Push this button to adjust the contrast.   

TEST

: The test checks the complete protection system (DE B and D Toroids  T.C.). Push quickly the test button to start the test. Display becomes red. 

TRIP relay and the 2

nd

 relay change state. Danger signal and message “TRIP” appear flashing. Press “RESET” button to reset, if the reset mode is set as manual mode 

(MAN). 

Note

: In case of strong electromagnetic disturbances the display may go blank or irregular: push the button 

 

to restore the normal display.  

SETUP (BLU DISPLAY) 

(for 6Din version the keys are on 

the right side) 

CAL= 

button for toroids calibration. This operation must be perfomed in total absence of differential current dispersion. Enter in 

SETUP, by pushing SET button for at least 3 sec (blue display), then pushing quickly for two times CAL button. The display appears 
violet  and  the  device  make  the  calibration  automatically.  This  operation  is  absolutely  necessary  for  commissioning  of  the 
instrument. If calibration will be good, the display backs to blue and it will no longer be necessary repeat this procedure. It's not 
possible make calibration if an important alarm is detected by device (ALA – TRIP - TORO). 
 
1 -

push SET button for at least 3 seconds to enter in SET UP (

display becomes blue). 

2- push quickly SET button to select cyclically the parameter to modify (it will appear flashing). 
3- push 

▲▼

 

buttons

 

to modify the selected parameter. 

4- 

push SET button for at least 3 seconds to exit from SETUP and save the parameters 

(display returns green). 

DER3BDUAL automatically exits from SETUP without saving modification, after 3 minutes of inactivity. 

Note

: The new setup parameters will be operative only after saving. If an alarm occurs in setup, it is caused by the previously set parameters.  

PARAMETERS 

RANGE

 

[DEFAULT] 

IΔn (A)= 

Threshold of the nominal residual current: when IΔ exceeds I∆n, the TRIP relay switches.

 

0,05 ÷ 7A 

[0,05A] 

ΔT= 

Limiting non-actuating time. If you set it to "INST", the tripping mode becomes instantaneous.

 

0,06 ÷ 5sec 

[0.060

S

T – 

The

 

2

nd

 relay is a second TRIP relay: it switches at the same time of TRIP relay (the trip coil must be

 always 

connected to TRIP relay). 

A – 

The

 

2

nd

 relay is an alarm relay. It switches when set alarm threshold is exceeded. 

T/ A 

[A]

 

N.de. =

 Trip relay is normally de-energized (N.De.) and it energizes when IΔ overcomes IΔn.  

NE= 

Trip relay is normally energized (N.E.) and it de-energizes when IΔ overcomes IΔn. 

Warning: 

the safety condition N.E, is applied 

exclusively to the TRIP relay and not to second relay, even if it is set in TRIP condition. Setting the positive security (fail safe) excludes the 
permanent verification of the T.C. circuit and its power.

 

N.De. - N.E. 

[N.De.]

 

MAN/AUTO

: Reset mode: manual or automatic. After a trip for IΔ> IΔn, the written "SET" becomes "RESET" and will therefore allow the 

RESET of the TRIP condition (only if IΔ <IΔn) 

MAN- AUTO 

[MAN]

 

 

AL

:  Threshold of Alarm (% di IΔn). When this threshold is exceeded, an alarm condition will be generated. 

20% ÷ 80% 

[50%]

 

<R

: Hysteresis: threshold in percentage value of IΔn.  

30% ÷ 80% 

[80%]

 

KCT

= transformation ratio of toroid DON'T CHANGE THIS PARAMETER .

 

 

BA AL

= When “ON” the continuity, the connections and the power supply of  T.C.  are continuously monitored and an alarm will be 

generated in case of malfunction.  

ON-OFF 

[ON]

 

NODE

= Configuration network node: assign to each DER3BDUAL a node number (only for versions equipped with serial output RS485)

 

 

1 ÷ 247 

[1]

 

BAUD

= Serial baudrate configuration (only for versions equipped with serial output RS485) 

4800 ÷ 38400 

[19200]

 

 

Summary of Contents for DER3BDUAL

Page 1: ...t Inst 0 06 5sec In Massima corrente nominale Maximum rated current D35 D60 D80 D110 D160 D210 Categoria sovratensione Overvoltage category Grado inquinamento Pollution degree CAT III 2 480A 720A 1020A 1560A 1860A 2160A Collegamenti toroide relè Connections toroid MRCD Cavi schermati twistati Shielded twisted cables Involucro Housing Classe di isolamento Insulation class II sul frontale II on the ...

Page 2: ...dei toroidi Tale operazione va eseguita in totale assenza di corrente differenziale Entrati in SETUP premendo il tasto di SET per 3 sec display azzurro sarà necessario premere due volte velocemente il tasto CAL Il display si colora di viola e il dispositivo esegue la calibrazione automaticamente Questa operazione è assolutamente necessaria per la messa in servizio dello strumento Se la calibrazion...

Page 3: ...are on the right side CAL button for toroids calibration This operation must be perfomed in total absence of differential current dispersion Enter in SETUP by pushing SET button for at least 3 sec blue display then pushing quickly for two times CAL button The display appears violet and the device make the calibration automatically This operation is absolutely necessary for commissioning of the ins...

Page 4: ...oltage or no armed circuit breaker WARNING Disable this monitoring if no TC is used in the system TRIP rosso fisso Red Il rele di Trip e il 2 rele cambiano di stato Incremento dell istogramma Blocco della visualizzazione sul valore di corrente per cui è avvenuto l intervento The Trip relay and the 2nd relay change state The increasing of histogram The visualization is blocked on current value for ...

Reviews: