frequency.
After tracking it it will continue to accelerate to reach the set frequency.
P095 Frequency track Current Level
Set Range: 0~200% Unit: 1% Factory Setting: 150
When the inverter search speed this set value sould be taken as the level for output current. When
the output current is higher than this level the inverter will suspend searching. When the current is
restored below the current level it will then execute the frequency track again.
After starting the frequency track please decrease properly the frequency track current level
according to the actual conditionof load. Otherwise it is extremely easy to cause overcurrent protection.
P096 Restart after Instantaneous Stop
Set Range: 0~1 Factory Setting: 0
0: Invalid, i.e. the inverter will not restart after an instantaneous stop.
1: Frequency track Start. Refer to P094.
P097 Allowable Power-off Time
Set Range: 0.1~5.0S Unit: 0.1S Factory Setting: 0.5
This parameter is set for the maximum allowable power off time. If exceeding the set time the
inverter will continue to stop input after power on. To execute the restart it needs to follow the general
starting procedures.
*Attention: When using this function special attention should be paid to the safety. During the
process of instantaneous power off and power on the inverter may restart. It is easy to produce danger.
Be careful to use this function.
P098 Number of Abnormal Restart
Set Range: 00~10 Unit: 1 Factory Setting: 00
After the abnormal conditions (such as overcurrent, overvoltage) happen the invrter will
automatically reset and restart. If the starting mode is set for general mode it will start according to
the general mode. If it is set for frequency track start it will start in the frequency track mode. After
start it will restore the set number again if there is not anything unusual happened within 60 seconds.
If there is any error and it reaches the set number the inverter will not have input. It can only be started
after reset. If P098 is set to 0 the inverter will not carry out the functions of automatic reset and restart.
P099 Auto Voltage Regulation
Set Range: 0~1 Unit: 1 Factory Setting: 1
0: Invalid
1: Valid
When the input power supply is not stable and if the voltage is over high the operation of the
motot with the power of exceeding the rated voltage will cause the temperature of the motor increasing,
the insulation damaged and the output torque unstable. This auto voltage regulation can automatically
stablize the output voltage within the rated voltage range of the motor under the condition of unstable
output power supply
When this function is set to invalid the output voltage will fluctuate.